Nibe VVM 310 Скачать руководство пользователя страница 46

mixing valve amplifier

Setting range: 0.1 –10.0

Default value: 1.0

mixing valve step delay

Setting range: 10 – 300 s

Default values: 30 s

Set when the addition is to start, the minimum run time and
the minimum temperature for external addition with shunt
here. External addition with shunt is for example a
wood/oil/gas/pellet boiler.

You can set shunt valve amplification and shunt valve
waiting time.

Selecting "prioritised additional heat" uses the heat from
the external additional heat instead of the heat pump. The
shunt valve is regulated as long as heat is available, other-
wise the shunt valve is closed.

TIP

See the accessory installation instructions for
function description.

MENU 5.3.3 - EXTRA CLIMATE SYSTEM

use in heating mode

Setting range: on/off

Factory setting: on

use in cooling mode

Setting range: on/off

Factory setting: off

mixing valve amplifier

Setting range: 0.1 – 10.0

Default value: 1.0

mixing valve step delay

Setting range: 10 – 300 s

Default values: 30 s

Contr. pump GP10

Setting range: on/off

Factory setting: off

Here, you select which climate system (2 - 8) you wish to
set.

use in heating mode: If the heat pump is connected to a cli-
mate system(s) for cooling, any condensation can take place
in this/these. Check that "use in heating mode" has been
selected for the climate system(s) that is/are not adapted
for cooling. This setting means that the sub-shunt for the
extra climate system closes when cooling operation is activ-
ated.

use in cooling mode: Select "use in cooling mode" for climate
systems that are adapted to handle cooling. For 2-pipe
cooling you can select both "use in cooling mode" and "use
in heating mode", while for 4-pipe cooling you can only se-
lect one option.

Caution

This setting option only appears if the heat pump
is activated for cooling operation in menu 5.2.4..

mixing valve amplifier, mixing valve step delay: Here, you
set the shunt amplification and shunt waiting time for the
various extra climate systems that are installed.

Contr. pump GP10: Here, you can set the speed of the circu-
lation pump manually.

See the accessory installation instructions for function de-
scription.

MENU 5.3.4 - SOLAR HEATING

start delta-T

Setting range: 1 – 40 °C

Default value: 8 °C

stop delta-T

Setting range: 0 – 40 °C

Default value: 4 °C

max. tank temperature

Setting range: 70 – 85 °C

Default value: 85 °C

max. solar collector temp.

Setting range: 80 – 200 °C

Default value: 125 °C

max solar pool temperature

Setting range: 10 – 80 °C

Default value: 30 °C

anti-freeze temperature

Setting range: -20 – +20 °C

Default value: 2 °C

start solar collector cooling

Setting range: 80 – 200 °C

Default value: 110 °C

start delta-T, stop delta-T: Here, you can set the temperat-
ure difference between solar panel and solar tank at which
the circulation pump will start and stop.

max. tank temperature, max. solar collector temp.: Here,
you can set the maximum temperatures in the tank and
solar panel respectively at which the circulation pump will
stop. This is to protect against excess temperatures in the
solar tank.

NIBE VVM 310

Chapter 8 | Control – Menus

46

Содержание VVM 310

Страница 1: ...Installer manual Indoor module NIBE VVM 310 EMK IHB EN 2235 1 731202...

Страница 2: ...described on page 37 Set the indoor climate 2X MY INSTALLATION INDOOR CLIMATE HOT WATER INFO The mode for setting the indoor temperature is accessed by pressing the OK button twice when in the start m...

Страница 3: ...4 Optional connections 28 Connecting accessories 29 6 Commissioning and adjusting 29 Preparations 29 Filling and venting 30 Start up and inspection 32 Setting the heating curve 33 Cooling in 2 pipe sy...

Страница 4: ...lashes cannot cause harm The entire length of the overflow pipe must be inclined to prevent water pockets and must also be frost proof The overflow pipe must be at least the same size as the safety va...

Страница 5: ...ction must be carried out by a suitably qualified person In addition fill in the page for the installation data in the User Manual Date Signature Notes Description Heating medium see section System di...

Страница 6: ...Part no 064 220 S2125 12 3x400V Part no 064 217 S2125 12 1x230V Part no 064 218 NIBE SPLIT HBS 05 HBS 05 12 Part no 067 480 AMS 10 12 Part no 064 110 HBS 05 16 Part no 067 536 AMS 10 16 Part no 064 0...

Страница 7: ...se water can exit the safety valve1 for hot water when connected to VVM 310 the space where VVM 310 is placed must be provided with a floor drain 1 Not enclosed INSTALLATION AREA Leave a free space of...

Страница 8: ...panels can be removed to make installation easier Caution 50 mm space required to remove the side panels 1 Remove the screws from the upper and lower edges 2 Twist the panel slightly outwards 3 Move...

Страница 9: ...UB2 BF1 BT6 BT54 XL30 AA7 XL18 XL3 XL4 XL8 XL19 QN11 AA1 X3 BT30 AA1 X1 AA1 X7 AA1 S2 AA1 AA3 X4 BP5 QN35 K1 PZ3 XL1 XL2 BT3 BT2 AA4 W130 SF1 QN10 BT7 XL9 PZ1 PZ4 FQ10 S2 Applies to VVM 310 EMK Availa...

Страница 10: ...r display BT7 Thermostat standby mode BT30 Sensor external heat source tank BT54 Temperaturesensor heatingmediumsupplyafterimmer sion heater BT63 1 Not visible in the image ELECTRICAL COMPONENTS Immer...

Страница 11: ...efrost ing 100 pump speed l s Air waterheat pump 22 20 0 19 F2050 6 F2050 10 Minimum re commended pipe dimen sion mm Minimum re commended pipe dimen sion DN Minimum flow duringdefrost ing 100 pump spe...

Страница 12: ...in VVM 310 for calculating expansion vessel is 250 l The expansion vessel s volume must be at least 5 of the system s total volume Example table Volume l ex pansion vessel Total volume l indoor module...

Страница 13: ...M VVM 310 consists of hot water coil for hot water heating immersion heater circulation pumps buffer vessel and control system VVM 310 connects to the climate system VVM 310 is directly adapted for co...

Страница 14: ...1 Connection heating medium return line G20 int XL2 Connection cold water G20 int XL3 Connection hot water G20 int XL4 Connection docking from heat pump G20 int XL8 Connection docking to heat pump G20...

Страница 15: ...ystem is a system that regulates the indoor temperature with the help of the control system in VVM 310 and for example radiators underfloor heating underfloor cooling fan coils etc CONNECTING THE CLIM...

Страница 16: ...ersion heater In a water heater with an immersion heater the water is initially heated by the heat pump The immersion heater in the water heater is used for keeping warm and when the heat pump does no...

Страница 17: ...t be set to or until the boiler has been filled with water and the radi ator system vented Otherwise the temperature limiter thermostat and the immersion heater can be damaged NOTE If the supply cable...

Страница 18: ...f the electrical boxes is opened using a screwdriver NOTE The cover for the input card is opened without a tool Removing the cover input circuit board 1 2 1 Push the catch down 2 Angle out the cover a...

Страница 19: ...CABLE LOCK Use a suitable tool to release lock cables in the indoor module terminal blocks LEK 1 2 2 3 1 2 3 3 4 1 2 LEK 1 1 2 2 3 3 1 2 3 3 4 1 2 1 2 19 Chapter 5 Electrical connections NIBE VVM 310...

Страница 20: ...ature sensor BT25 needs to be used connect it to terminal block X6 5 and X6 6 on the input board AA3 Use a 2 core cable with a cable area of at least 0 5 mm F1245 4 5 6 7 AA3 X6 BT25 VVM 310 EXTERNAL...

Страница 21: ...r It is important that the sensor is not pre vented from measuring the correct room temperature for example by being located in a recess between shelves be hind a curtain above or close to a heat sour...

Страница 22: ...310 and F2040 F2050 NIBE SPLIT HBS 05 20 AA23 X4 B A GND B A GND 5 4 3 2 1 6 Inomhusmodul AA3 X4 B GND A 14 13 12 11 10 15 F2040 HBS 05 VVM 310 F2040 HBS 05 20 VVM 310 and F2120 S2125 Inomhusmodul F21...

Страница 23: ...er than the set fuse size the power step is not allowed to cut in See chapter Load monitor on page 24 EMERGENCY MODE When the indoor module is set to emergency mode SF1 is set to only the most necessa...

Страница 24: ...sensors NOTE If the installed air water heat pump is frequency controlled it will be limited when all power stages are disconnected A current sensor should be installed on each incoming phase conducto...

Страница 25: ...r NC stove monitor for accessory ERS Stove monitor is a thermostat that is connected to the chimney When the negative pressure is too low the fans in ERS NC are switched off pressure switch for climat...

Страница 26: ...he Software tab to download the latest software to your installation Caution In systems with both underfloor heating and ra diators NIBE ECS 40 41 should be used for op timum operation External blocki...

Страница 27: ...cooling is activated by the temperature of the outdoor temperature sensor BT1 and any room sensor BT50 room unit or separate room sensor for cooling BT74 if two different rooms are to be heated or co...

Страница 28: ...LiYY EKKX or similar Refer to the accessory manual for further instructions 1 2 3 4 5 6 7 8 AA5 X4 15 A B GND A B GND A B GND A B GND A B GND 14 13 AA3 X4 1 2 3 4 5 6 7 8 AA5 X4 Indoor module Accessor...

Страница 29: ...e system are filled with water 3 When the water exiting the vent valve QM20 is not mixed with air close the vent valves After a while the pressure rises on the externally mounted pressure gauge When t...

Страница 30: ...rwards to help vent VVM 310 Caution As long as the start guide is active no function in VVM 310 will start automatically The start guide will appear at each restart of VVM 310 until it is deselected o...

Страница 31: ...lves using control and external heating requirement Available pressure circulation pump GP1 0 10 20 30 40 50 60 70 80 0 0 0 1 0 2 0 3 0 4 0 5 Tillg ngligt tryck kPa Vattenfl de l s 20 100 40 60 80 Flo...

Страница 32: ...ther adjustment CURVE OFFSET An offset of the heating curve means that the supply tem perature changes by the same amount for all outdoor tem peratures e g a curve offset of 2 steps increases the supp...

Страница 33: ...ettings for the climate system are adjusted in the indoor climate menu menu 1 Setting hot water circulation operating time Setting range 1 60 min Factory setting 60 min downtime Setting range 0 60 min...

Страница 34: ...peration immersion heater not permitted With over capacity mode of SG Ready the hot water is set to activate temp lux immersion heater permitted affect cooling accessory required Here you set whether...

Страница 35: ...oor module display is not illuminated and the status lamp illuminates yellow F USB PORT The USB port is hidden beneath the plastic badge with the product name on it The USB port is used to update the...

Страница 36: ...that blocks one of them Blocking the compressor Blocking additional heat This symbol appears if periodic increase or lux mode for the hot water is activated This symbol indicates whether holiday setti...

Страница 37: ...another option 1 Mark the applicable option One of the options is pre selected white 2 Press the OK button to confirm the selected option The selected option has a green tick SETTING A VALUE time dat...

Страница 38: ...ows Current menu window Number of windows in the menu Scroll through the windows in the start guide language 4 6 If the start guide is left on this page it closes automatically in 60 min Arrows to scr...

Страница 39: ...ting curve 1 9 1 curve 1 9 advanced 1 9 1 2 cooling curve 1 9 2 external adjustment 1 9 3 1 heating 1 9 3 min flow line temp 1 9 3 2 cooling 1 9 4 room sensor settings 1 9 5 cooling settings 1 9 6 fan...

Страница 40: ...TER 2 2 comfort mode 2 3 scheduling 2 9 2 hot water recirc 2 9 advanced Menu 3 INFO 3 1 service info 3 INFO 3 2 compressor info 3 3 add heat info 3 4 alarm log 3 5 indoor temp log Accessories are need...

Страница 41: ...iods electricity 4 1 8 6 tariff per ext shunt add 4 1 8 7 tariff per ext step add 4 1 8 8 tariff periods OPT10 Menu 4 1 10 solar electricity 4 2 op mode 4 3 my icons 4 4 time date 4 6 language 4 7 hol...

Страница 42: ...ettings 5 2 4 accessories 5 3 2 shunt controlled add heat 5 3 accessory settings 5 3 3 extra climate system 5 3 4 solar heating 5 3 7 external addition 5 3 11 modbus 5 3 12 exhaust supply air module 5...

Страница 43: ...temp lux 58 C Here you set the start and stop temperature of the hot water for the different comfort options in menu 2 2 MENU 5 1 2 MAX FLOW LINE TEMPERATURE climate system Setting range 5 80 C Defaul...

Страница 44: ...for cooling you can also set the heating medium pump speed during active respectively cooling operating modes the heating medium pump then runs in manual operation MENU 5 1 12 INTERNAL ELECTRICAL ADDI...

Страница 45: ...ned curves You set a curve for a demand heat hot water etc by un ticking auto turning the control knob until a temperature is marked and pressing OK You can now set at what temper atures the max and m...

Страница 46: ...cooling operation is activ ated use in cooling mode Select use in cooling mode for climate systems that are adapted to handle cooling For 2 pipe cooling you can select both use in cooling mode and us...

Страница 47: ...n 10 the address can be set between 1 247 Earlier versions have a fixed address ad dress 1 Here you can select if you want to have word swap instead of the preset standard big endian See the accessory...

Страница 48: ...ou select which pump to use in the system MENU5 3 21 FLOWSENSOR ENERGYMETER Supply temperature sensor set mode Setting range EMK150 EMK300 310 EMK500 Factory setting EMK150 energy per pulse Setting ra...

Страница 49: ...be a heating cooling or hot water de mand to start the compressor NOTE Do not quick start the compressor too many times over a short period of time as this could damage the compressor and its surroun...

Страница 50: ...s 100 Set the speed at which the charge pump is to operate in the present operating mode Select auto if the speed of the charge pump is to be regulated automatically factory set ting for optimal opera...

Страница 51: ...onal heat are active The electrical additional heat power in emer gency mode is set in the immersion heater board AA1 See page 23 for instructions EMPTYING THE HOT WATER COIL The hot water coil is mos...

Страница 52: ...ect file can be selected through choose another file start updating Select start updating if you want to start the update You are asked whether you really want to update the software Respond yes to co...

Страница 53: ...g activated A log file is now created where the temperature and the immersion heater output can be read off Logging contin ues until logging floor drying activated is deselected or until floor drying...

Страница 54: ...sed the alarm reset alarm In many cases it is sufficient to select reset alarm for the product to revert to normal operation If a green light comes on after selecting reset alarm the alarm has been re...

Страница 55: ...lected select a higher value on stop heating in menu 4 9 2 If mode manual is selected select heating If this is not enough select addition Too low set value on the automatic heating control Enter menu...

Страница 56: ...running the heat pump in add heat only This means that additional heating only is used to heat the house SET THE INSTALLATION TO ADDITIONAL HEAT MODE 1 Go to menu 4 2 op mode 2 Mark add heat only usin...

Страница 57: ...e control module controls F135 Part no 066 075 The accessory requires that NIBE air water heat pump is installed HRV UNIT ERS This accessory is used to supply the accommodation with energy that has be...

Страница 58: ...Dimensions 20 1780 560 600 355 245 615 95 185 215 30 50 80 135 190 80 135 190 300 NIBE VVM 310 Chapter 12 Technical data 58 Technical data...

Страница 59: ...ump connections G20 int Connection for expansion vessel Miscellaneous Indoor module 17 litre Volume hot water coil 270 litre Volume total indoor module 50 litre Volume buffer vessel 1 0 10 bar MPa bar...

Страница 60: ...400 V Part Specification Sheet 450232 4 Page 2 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 12 16 400V 3N 50Hz 12kW WIRING DIAGRAM VVM 310 ELSCHEMA VVM 310 450232 4 NIBE VVM 31...

Страница 61: ...cation Sheet 450232 4 Page 3 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 12 16 400V 3N 50Hz 12kW WIRING DIAGRAM VVM 310 ELSCHEMA VVM 310 450232 4 61 Chapter 12 Technical data N...

Страница 62: ...cation Sheet 450232 4 Page 4 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 12 16 400V 3N 50Hz 12kW WIRING DIAGRAM VVM 310 ELSCHEMA VVM 310 450232 4 NIBE VVM 310 Chapter 12 Techni...

Страница 63: ...cation Sheet 450232 4 Page 5 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 12 16 400V 3N 50Hz 12kW WIRING DIAGRAM VVM 310 ELSCHEMA VVM 310 450232 4 63 Chapter 12 Technical data N...

Страница 64: ...cation Sheet 450232 4 Page 6 6 Created 2017 12 01 09 37 0 001 MJN 2017 12 01 Production GBN 2011 12 16 400V 3N 50Hz 12kW WIRING DIAGRAM VVM 310 ELSCHEMA VVM 310 450232 4 NIBE VVM 310 Chapter 12 Techni...

Страница 65: ...ernatives Two or more climate systems 16 Draining the climate system 51 Draining the hot water heater 51 E Electrical addition maximum output 23 Power steps of the immersion heater 23 Electrical circu...

Страница 66: ...X inputs 25 Possible selection for AUX output potential free variable relay 26 Post adjustment venting 31 Power connection 20 Preparations 29 Pump speed 31 R Recovery 5 Removing panels 8 Removing the...

Страница 67: ...e 3 01510 Vantaa Tel 358 0 9 274 6970 info nibe fi nibe fi NORWAY NETHERLANDS GREAT BRITAIN ABK Qviller AS Brobekkveien 80 0582 Oslo Tel 47 23 17 05 20 post abkqviller no nibe no NIBE Energietechniek...

Страница 68: ...ems All product illustrations facts and data are based on the available information at the time of the publication s approval NIBE Energy Systems makes reservations for any factual or printing errors...

Отзывы: