Caution
If you need to adjust "min. flow line temp." and/or
"max flow line temperature", you do this in other
menus.
Settings for "min. flow line temp.” in menu 1.9.3.
Settings for "max flow line temperature” in menu
5.1.2.
Caution
Curve 0 means that "own curve" is used.
Settings for "own curve" are made in menu 1.9.7.
TO READ OFF A HEATING CURVE
1.
Turn the control knob so that the ring on the shaft with
the outdoor temperature is marked.
2. Press the OK button.
3. Follow the grey line up to the curve and out to the left
to read off the value for the supply temperature at the
selected outdoor temperature.
4. You can now select to take read outs for different out-
door temperatures by turning the control knob to the
right or left and read off the corresponding flow temper-
ature.
5. Press the OK or Back button to exit read off mode.
Cooling in 2-pipe system
VVM 310 contains a built-in function for operating cooling
in a 2-pipe system down to 17 °C, factory setting 18 °C. This
requires that the outdoor module can perform cooling. (See
the Installer Manual for your air/water heat pump.) If the
outdoor module can perform cooling, the cooling menus are
activated in the display on the indoor module (VVM).
In order for operating mode “cooling” to be permitted, the
average temperature must be above the setting value for
“start cooling” in menu 4.9.2
The cooling settings for the climate system are adjusted in
the indoor climate menu, menu 1.
Setting hot water circulation
operating time
Setting range: 1 – 60 min
Factory setting: 60 min
downtime
Setting range: 0 – 60 min
Factory setting: 0 min
Set the hot water circulation for up to three periods per day
here. During the set periods the hot water circulation pump
will run according to the settings above.
"operating time" decide how long the hot water circulation
pump must run per operating instance.
"downtime" decide how long the hot water circulation pump
must be stationary between operating instances.
NOTE
Hot water circulation is activated in menu 5.4 "soft
inputs and outputs".
Pool
(ACCESSORY IS REQUIRED)
start temp
Setting range: 5.0 – 80.0 °C
Factory setting: 22.0 °C
stop temperature
Setting range: 5.0 – 80.0 °C
Factory setting: 24.0 °C
Select whether the pool control is to be activated and within
what temperatures (start and stop temperature) pool heating
must occur.
When the pool temperature drops below the set start tem-
perature and there is no hot water or heating requirement,
VVM 310 starts pool heating.
Untick "activated" to switch off the pool heating.
Caution
The start temperature cannot be set to a value
that is higher than the stop temperature.
SG Ready
This function can only be used in mains networks that sup-
port the "SG Ready"-standard .
Make settings for the function "SG Ready" here.
Low price mode means that the electricity supplier has a
low tariff and the system uses this to reduce costs.
33
Chapter 6 | Commissioning and adjusting