![Nibe DVC 10-50 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/nibe/dvc-10-50/dvc-10-50_user-manual_1686182023.webp)
www.nibe.com
23
CONFIGURING THE UNIT IN SLAVE MODE ACCORDING TO THE DIAGRAM NO. 2
•
Start the software at your PC to set up the unit.
•
Connect the ventilator to a PC using a USB to mini USB cable.
•
Select a required device from the dropdown list (1).
•
Select Slave for required device mode (2).
•
Select With Wi-Fi router for the connection type (3).
•
Open the tab Wi-Fi (4).
•
Press Search Wi-Fi (5). It is an optional requirement.
•
Enter or select from the list the name of a wireless access point of the router (6).
•
Enter Wi-Fi password for the router (7).
•
Set a unique number for each Slave unit (8) from 1 to 32 in the consequent order. Check the busy numbers using the installed mobile application,
see page 20.
•
Enter the IP address of the Master unit (10) for the Slave unit to be connected.
•
Set the Slave IP address (9). It is an optional requirement.
)
Set
DHCP
to enable automatic assigning of the IP address during connection to router.
)
Set
Static
to enable manual assigning of the IP address for the Slave unit. The assigned address must match the current network and be unique.
Detection of a free IP address is described below.
•
Apply and save the selected parameters (11).
•
If all the parameters are entered correct and the Master unit is turned on, within 10 seconds the tab (12) is displayed as Master connected and the tab
(13) as Wi-Fi connected.
Detection of a free IP address for the Slave unit is as follows:
1.
Open the window of the command line: press combination Win+R and enter «cmd» in the appeared window «Run», then press Enter.
2.
Select the command «ipconfig» in the appeared window and press Enter.
3.
The line «Default gateway» indicates the router IP-address. Example: «Basic gateway . . . . . . . : 192.168.0.1».
4.
Detect a free IP address for the Slave unit: enter the command «ping» in the command line, IP-address of the router, change the fourth address
field from 1 to 254 and press Enter until the line «This node is not available» appears. Example: «ping 192.168.0.3»+»Enter».
5.
Enter the selected available address in the field Slave IP address» for setup of the ventilator.