![Nibe DVC 10-50 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/nibe/dvc-10-50/dvc-10-50_user-manual_1686182017.webp)
www.nibe.com
17
RESET FILTER TIMER FOR DVC 10-50W(L)
•
Start the program NIBE DVC 10.exe at your PC.
•
Connect the ventilator and PC using a USB to mini USB cable.
•
Select a required unit from the dropdown list
Select device
(1).
•
Select the tab
Filter
.
•
Press the button
Reset filter timer
(3) to reset the timer. After replacement of the filters the operating hours are displayed above the button (2).
EMERGENCY SHUTDOWN OF THE UNIT DVC 10-50W(L)
Emergency shutdown of all the ventilators happens if the fan shutdown lasts above 5 seconds. In case of emergency shutdown of any ventilator in a
network all the other ventilators also stop.
Alarm is confirmed by a respective alarm indication for all the ventilators in the network, see page 14.
To reset the alarm troubleshoot the motor jam, turn the ventilator off and restart it using the button
on the indoor unit or the button
on
the remote control.
If the alarm indication is still active, please refer to the Seller. Cut off power supply to a defective unit to enable operation of the other units in the network.