54
NIBE BA-SVM 10-200
NOTE
You cannot set “stop add. heat” higher than “stop heat-
ing”.
NOTE
After factory setting, personal settings such as heating
curves must be reset.
NOTE
In systems where heating and cooling share the same
pipes, „stop heating” cannot be set higher than „start
cooling” if there is no cooling/heating sensor.
NOTE
A higher value for „start compressor” causes more
frequent compressor starts, which increases wear on
the compressor. Too low a value can give uneven indoor
temperatures.
NOTE
Long term blocking can cause reduced comfort and op-
erating economy.
Menu 4.9.3 - Degree minute value
Menu 4.9.4 - Factory setting user
Menu 4.9.5 - Blocking sched.
Degree minutes are a measurement of the current
heating demand in the house and determine when the
compressor or additional heat will be started/stopped.
For more information select “?".
All settings that are available to the user (including ad-
vanced menus) can be restored to default values here.
For more information select "?".
The compressor can be scheduled to be blocked for
up to two different time periods here. When sched-
uling is active, the actual blocking symbol in the main
menu on the heat pump symbol is displayed. For more
information select "?".
Factory settings:
Current value: 0 DM
Start compressor: -60 DM
start diff. add. heat: 400 DM
diff. between additional steps: 30 DM
TIP
If you wish to set similar scheduling for every day of
the week, start by filling in “all” and then change the
desired days.
TIP
Set the finish time earlier than the start time so that
the period extends beyond midnight. Scheduling then
stops at the set finish time the day after.
Scheduling always starts on the same day as the start
time is set.
Factory settings:
Stop heating: 17°C
Stop add. heat: 5°C
Filtering time: 24 hrs
Section 9 |
Control