PROGRAM SETTINGS
Caution
The cooling function must be activated in the
heat pump. See the Installer Manual for the
relevant model.
Program setting of AXC 30 can be performed via the
start guide or directly in the menu system.
START GUIDE
The start guide appears at first start-up after the heat
pump installation, but it can also be found in menu 5.7.
MENU SYSTEM
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 5.2.4 -accessories
Activating/deactivating of accessories.
Select: "active cooling 4 pipe".
Menu 1.1 -temperature
Setting of indoor temperature (room temperature sensor
is required).
Menu 1.9.3.2 - min. flow line temp.
You can set the min supply temperature for cooling here.
Menu 1.9.5 - cooling settings
Here you can perform the following settings:
• Desired flow temperature at an outdoor air temperat-
ure of +20 and +40 °C.
• Time between cooling and heating operation and vice
versa.
• Selection of room sensor can control cooling.
• How much the room temperature may decrease or
increase compared to the desired temperature before
switching to heating respectively cooling (requires
room sensor).
• Degree minute levels for cooling.
Menu 4.9.2 -auto mode setting
When heat pump operating mode is set to "auto“ it se-
lects when start and stop of additional heat, heat produc-
tion and cooling is permitted, dependent on the average
outdoor temperature.
Select the average outdoor temperatures in this menu.
You can also set the time over which (filtering time) the
average temperature is calculated. If you select 0, the
present outdoor temperature is used.
Menu 5.6 -forced control
Forced control of the different components in the heat
pump as well as in the different accessories that may
be connected.
EQ1-AA5-K1: Signal to reversing valve (QN12).
EQ1-AA5-K3: Signal cooling circulation pump (GP10).
Caution
Also see the Installer Manual for the main
product.
71
AXC 30 F-series | GB
F
Содержание AXC 30
Страница 1: ...Installer manual Accessory card IHB 2113 3 231464 AXC 30 UN ...
Страница 2: ...S series S1255 4 S series F series 45 F series ...
Страница 12: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 AXC 30 S series GB 12 S ...
Страница 53: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 53 AXC 30 F series GB F ...