Extra climate system
GENERAL
This function is used when SMO S40 is going to control
more than one climate system. It is possible to connect
up to eight different climate systems (heating and/or
cooling systems) that require different supply temperat-
ures, for example where the house has both radiator
systems and underfloor heating systems.
Caution
With underfloor heating systems, the maxim-
um supply temperature is normally set
between 35 and 45 °C.
Check the max floor temperature with your
floor supplier.
Caution
If a room sensor is used in a room with under-
floor heating, it should only have an indicatory
function, not control of the room temperature.
PIPE CONNECTIONS
GENERAL
When connecting extra climate systems, they must be
connected so that they have a lower working temperat-
ure than the climate system 1.
CIRCULATION PUMP
The extra circulation pump (EP21-GP10) is positioned in
the extra climate system according to the outline dia-
gram.
SHUNT VALVE
The shunt valve (EP21-QN25) is located on the supply
line after the heat pump/indoor module, before the first
radiator in the climate system 1. The return line from
the extra climate system is connected to the shunt valve
and to the return line from the climate system 1, see
image and outline diagram.
B
A
AB
• Connect the supply line to the climate
system from the heat pump to port A on
the shunt valve (opens on increase signal)
• Connect the return line from the climate
system to port B on the shunt valve via
the T-pipe (closes on reduce signal).
• Connect the supply line to the climate system to the
common port AB on the shunt valve (always open).
TEMPERATURE SENSOR
• The supply line sensor (EP21-BT2) is installed on the
pipe between the circulation pump (EP21-GP10) and
shunt valve (EP21-QN25).
• The return line sensor (EP21-BT3) is installed on the
pipe from the extra climate system.
LEK
LEK
E
Install the temperature sensors using cable ties, together
with the heat conducting paste and aluminium tape.
Then insulate with the enclosed insulation tape.
NOTE
To prevent interference, sensor cables to ex-
ternal connections must not be laid close to
high voltage cables.
SYSTEM DIAGRAM
Caution
This is an outline diagram. Actual installations
must be planned according to applicable
standards.
EXPLANATION
Climate system
EP21
AXC module
AA25
Flow temperature sensor, extra climate
system
BT2
Return line sensor, extra climate system
BT3
Circulation pump, extra climate system
GP10
Shunt valve
QN25
Non-return valve
RM1
SMO S40
AA35
External supply temperature sensor
BT25
External return line sensor
BT71
External heating medium pump
GP10
Non-return valve
RM1.2
-EP21-RM1
-EP21-GP10
-EP21-BT2
-EP21-AA25
-EP21-BT3
-EP21-QN25
-EP21
-AA35
-GP10
-AA35
-AA35
-BT25
-AA35-BT71
-RM1.2
17
AXC 30 S-series | GB
S
Содержание AXC 30
Страница 1: ...Installer manual Accessory card IHB 2113 3 231464 AXC 30 UN ...
Страница 2: ...S series S1255 4 S series F series 45 F series ...
Страница 12: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 AXC 30 S series GB 12 S ...
Страница 53: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 53 AXC 30 F series GB F ...