PROGRAM SETTINGS
Activating AXC 30 can be performed via the start guide
or directly in the menu system.
START GUIDE
The start guide appears upon first start-up after heat
pump installation, but is also found in menu 5.7.
MENU SYSTEM
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
Menu 5.2.4 - accessories
Activating/deactivating of accessories.
Here, you state which accessories are installed for the
compatible product.
To automatically identify connected accessories, select
"Search for installed accessories". It is also possible to
select accessories from the list manually.
Menu 5.1.2 - max flow line temperature
Setting the maximum flow temperature for each climate
system.
Menu 5.3.3 - extra climate system
Mixing valve settings for extra installed climate sys-
tem.
mixing valve amplification 2
Setting range: 0.1–10.0
Factory setting: 1.0
mixing valve step delay 2
Setting range: 10–300 s
Factory setting: 30 s
use in heating mode
Setting range: on/off
Factory setting: on
use in cooling mode
Setting range: on/off
Factory setting: off
Contr. pump GP10
Setting range: on/off
Control signal
Setting range: PWM / 0-10V
Manual speed
Setting range: 0-100%
Menu 1.1 - temperature
Setting the indoor temperature.
Menu 1.9.1.1 -heating curve
Setting the heat curve.
Menu 1.9.1.2 -cooling curve
Setting the cooling curve.
Menu 1.9.2 - external adjustment
Setting external adjustment.
Menu 1.9.3 - min. flow line temp.
Setting the minimum flow temperature for each climate
system.
Menu 1.9.4 - room sensor settings
Activating and setting the room temperature sensor.
Menu 5.6 - forced control
Forced control of the different components in the heat
pump as well as in the different accessories that may
be connected. 2 is climate system, EP22, 3 is climate
system EP23, 4 is climate system EP21.
EP2#-AA5-K1: No function.
EP2#-AA5-K2: Signal (close) to mixing valve (QN25).
EP2#-AA5-K3: Signal (open) to mixing valve (QN25).
EP2#-AA5-K4: Activating the circulation pump (GP10).
Caution
Also see the Installer Manual for the main
product.
61
AXC 30 F-series | GB
F
Содержание AXC 30
Страница 1: ...Installer manual Accessory card IHB 2113 3 231464 AXC 30 UN ...
Страница 2: ...S series S1255 4 S series F series 45 F series ...
Страница 12: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 AXC 30 S series GB 12 S ...
Страница 53: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 53 AXC 30 F series GB F ...