Connecting charge
pumps in the case of
multiple heat pumps
GENERAL
This function allows control of up to two extra charge
pumps (GP12). AXC 30 is required for the charge pump
for slave - EB10X, with address 3 or higher. Up to eight
slaves can be combined in one system.
AA35-EB10X-GP12.X corresponds to AA35-EB103-
GP12.3, AA35-EB105-GP12.5 and AA35-EB107-GP12.7.
AA35-EB10Y-GP12.Y corresponds to AA35-EB104-
GP12.4, AA35-EB106-GP12.6 and AA35-EB108-GP12.8.
The control module controls the charge pumps together
with the relevant slave during heating, hot water or
cooling operation via AXC 30.
A type CPD charge pump is recommended to allow the
use of speed control, which guarantees correct delta-t
in the various operating modes during the year. AXC 30
also enables external blocking of each associated slave.
PIPE CONNECTIONS
The charge pump (GP12) is positioned in the relevant
charge circuit before joining with other charge circuits
or branching off different sub-systems via a reversing
valve.
SYSTEM DIAGRAM
Caution
This is an outline diagram. Actual installations
must be planned according to applicable
standards.
EXPLANATION
Heat pump
EB101-EB104
AXC module
AA25
Charge pump
GP12.1-GP12.4
Non-return valve
RM1
SMO S40
AA35
-EB104
-RM1
-AA35-GP12.1
-RM1
-RM1
-RM1
-EB101
-EB102
-EB103
-AA35
-EB103-AA25
-AA35-GP12.2
-AA35-GP12.3
-AA35-GP12.4
AXC 30 S-series | GB
38
S
Содержание AXC 30
Страница 1: ...Installer manual Accessory card IHB 2113 3 231464 AXC 30 UN ...
Страница 2: ...S series S1255 4 S series F series 45 F series ...
Страница 12: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 AXC 30 S series GB 12 S ...
Страница 53: ...ELECTRICAL CIRCUIT DIAGRAM WIRING DIAGRAM SHUNT CONTROL ELSCHEMA SHUNTSTYRD 051055 8 53 AXC 30 F series GB F ...