Alarm list
Reset/Rectify
Event
Cause
Name
The alarm is reset automatically
when the sensor is reconnected.
Ambient sensor (BT28): stopping
AMB 30 and compressor in NIBE
F1345.
Stated sensor short-circuited or
missing.
Sensor err. #
Other sensors: are only indicated
in the display.
Brine in (BT26): only shown in the
event of hybrid operation.
The alarm resets automatically
when the communication is re-
sumed.
Operation of AMB 30 and com-
pressor in NIBE F1345 is stopped.
No communication between dis-
play and AMB 30 (master unit of
several connected) for more than
3 minutes.
Communica-
tion
The alarm may be due to a cable
breakage, fault in the relay card
or fault in the display unit.
The alarm does not reset auto-
matically. Manual alarm reset is
required (restart of the control
unit).
Operation of AMB 30 (master
unit if several connected) and
compressor in NIBE F1345 is
stopped.
The fan overheating temperature
limiter has tripped.
Fläkt TL #
The fan starts again when the
ambient temperature rises above
the set value in menu
"BT28 min.".
Operation of AMB 30 is stopped.
Too low ambient temperature
(BT28).
Low BT28
The fan and the compressor are
permitted to start again when
the ambient temperature falls
below the set value set in
"BT28 max" menu by two de-
grees.
Operation of AMB 30 and com-
pressor in NIBE F1345 is stopped.
Too high ambient temperature
(BT28) (above 50 °C)
High BT28
# stands for which unit the fault the exists in.
37
Chapter 10 |
Disturbances in comfort
AMB 30
Содержание AMB 30
Страница 1: ...Installer manual LEK AMB 30 Accessories F1345 IHB GB 1341 1 231417 ...
Страница 2: ......
Страница 47: ...Electrical circuit diagram 45 Chapter 12 Technical data AMB 30 ...
Страница 48: ...AMB 30 Chapter 12 Technical data 46 ...
Страница 49: ...47 Chapter 12 Technical data AMB 30 ...
Страница 51: ......
Страница 52: ...NIBE AB Sweden Hannabadsvägen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu 231417 ...