The control unit, BCU 30 (AA25)
The control unit (AA25) is most easily positioned on
the wall where it is easy to access.
Unscrew the screw to open the control unit and access
the circuit board. The screw is underneath a rubber
cover on the front of the control unit (see image).
MR
OK
Remove the rubber
cover and unscrew the
screw to open the
control unit.
Connect the control unit using a 4-core cable to termin-
al block -COM1 on the relay card (AA6) as illustrated.
Suitable cable type is for example LiYY 4x0.50 or similar.
NOTE
The control unit is only connected to the main
unit (on installation of several AMB 30).
1
GND
COM1
COM2
A
B
GND
A
B
1
GND A B
Control unit,BCU 30
AMB 30
1
GND A B
AA6-COM1
AA6-COM2
AA25
Optional connections
Connecting several AMB 30
Up to 9 x AMB 30 can be connected to the same install-
ation.
Each unit can be set on the switch AA6-SF2 which states
which unit is which in the installation (the main unit =
1 etc.).
AA6-SF2
5
4
3
2
1
off
off
off
off
on
AMB
30 1
off
off
off
on
off
AMB
30 2
off
off
on
off
off
AMB
30 3
off
on
off
off
off
AMB
30 4
on
off
off
off
off
AMB
30 5
on
off
off
off
on
AMB
30 6
on
off
off
on
off
AMB
30 7
on
off
on
off
off
AMB
30 8
on
on
off
off
off
AMB
30 9
The units are connected in series where the main unit
is connected from COM2 on the relay card (AA6) to
COM1 on the relay card in the slave unit, which can be
repeated to the next slave unit etc. (see image). Suitable
cable type is for example LiYY 3x0.50 or similar.
23
Chapter 5 |
Electrical connections
AMB 30
Содержание AMB 30
Страница 1: ...Installer manual LEK AMB 30 Accessories F1345 IHB GB 1341 1 231417 ...
Страница 2: ......
Страница 47: ...Electrical circuit diagram 45 Chapter 12 Technical data AMB 30 ...
Страница 48: ...AMB 30 Chapter 12 Technical data 46 ...
Страница 49: ...47 Chapter 12 Technical data AMB 30 ...
Страница 51: ......
Страница 52: ...NIBE AB Sweden Hannabadsvägen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu 231417 ...