Settings - Sub menus
Fan
OK
OK
Systemtype
Settings
Testmanually
Service
Fan
Defrost
Stopairmode
Hybrid
Language
3.0K
Start
Diff1,2,3..
High/low
0.5K
15°C
Settings
Fan
Description
Sub menu
Fan
Here you can set the difference
between the temperature sensors
BT28 (ambient) and BT27 (brine out)
at which the fan is to start and stop.
Start
The fan starts when the set differ-
ence is exceeded and stops when the
temperature difference has fallen
below the set difference by approx
one degree.
Minimum running time for the fan
is 60 minutes.
Setting range: 1.0 – 6.0 K
Preset value: 3.0 K
Set what difference the differential
set in the menu "Start" must have
between different AMB 30 (if several
are installed) for start and stop.
Diff 1,2,3..
Setting range: 0.0 – 2.0 K
Preset value: 0.5 K
Here you select at what ambient
temperature (BT28) the fan must
shift between high and low speeds.
High/low
When the ambient temperature ex-
ceeds the set value the fan goes to
low speed and shifts to high speed
when the ambient temperature falls
below the set value by approxim-
ately one degree.
You can manually set the fan to
constant high or low speed.
Setting range: 8 – 20 °C, high (H) or
low (L)
Preset value: 10 °C
Defrost
OK
OK
Systemtype
Settings
Testmanually
Service
Fan
Defrost
Stopairmode
Hybrid
Language
Settings
1.5K
Startdiff
Timestab.
Stopactive
Pass./act.
Stoppass.
Maxtime
Interv.max
10min
12°C
3°C
1.0K
15min
3h
Defrost
Description
Sub menu
Defrost
Here you can set the difference
between the temperature sensors
BT28 (ambient) and BT27 (brine out)
at which defrosting of AMB 30 is to
start.
Start diff
Defrosting starts when the temperat-
ure difference exceeds the set value.
Setting range: 1.0 – 3.0 K
Preset value: 1.5 K
The stabilisation time for calculating
defrosting is shown here.
Time stab.
Fixed value: 20 min
Set the brine out (BT27) temperature
at which defrosting is to stop.
Stop active
Defrosting stops when the brine ex-
ceeds the set value.
Setting range: 8 – 20 °C
Preset value: 12 °C
Here you select at what ambient
temperature (BT28) the AMB 30
must shift between active and pass-
ive defrosting.
Pass./act.
Passive defrosting starts at the set
temperature and resumes active de-
frosting at the set temperature of
approx one degree.
Setting range: 1 – 9 °C
Preset value: 4 °C
AMB 30
Chapter 8 |
Control - Menus
30
Содержание AMB 30
Страница 1: ...Installer manual LEK AMB 30 Accessories F1345 IHB GB 1341 1 231417 ...
Страница 2: ......
Страница 47: ...Electrical circuit diagram 45 Chapter 12 Technical data AMB 30 ...
Страница 48: ...AMB 30 Chapter 12 Technical data 46 ...
Страница 49: ...47 Chapter 12 Technical data AMB 30 ...
Страница 51: ......
Страница 52: ...NIBE AB Sweden Hannabadsvägen 5 Box 14 SE 285 21 Markaryd info nibe se www nibe eu 231417 ...