NetPing server room environmental monitoring solutions and IP power distribution units.
Copyright © NetPing east Co., Ltd / E-mail:
/ Phone: +886-2-23121582
[email protected] www.netpingdevice.com
[8PWR] Sensors Plugin
Sensors 1-Wire
Sensors 1-Wire (
and
) connected to the connectors 1W plugs RJ12, allowed to use
extension cords or splitters. Maximum cable length 1-Wire network is limited to 50 meters.
Sensors of Dry Contact Type
Dry contact sensors are door opening sensors, buttons and other sensors, with a mechanism of work based on opening/closing a conductor. A
sensor is connected with two wires to an IO line of a device according to the table (an order of plugging wires does not matter).
Sensor Flex
NetPing 8/PWR-220 v4/SMS Terminal
First wire
One of IO lines – 1/2/3/4
Second wire
G
sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a
minimum cross section of 0,4 mm . Maximum allowable length of a flat cable is 100 m.
2
A leakage sensor is connected by a four-wire line according to the table.
Sensor Flex
NetPing 8/PWR-220 v4/SMS Terminal
Green
One of IO lines – 1/2/3/4
Yellow (White)
G
Red
+
Black
G
sensor, which are sequentially plugged one into another. Or it can be done independently with the help of any wire with a
minimum cross section of 0,4 mm . Maximum allowable length of a flat cable is 100 m.
2
A
is plugged by a two-wire line according to the table.
supply voltage sensor
An order of plugging wires does not matter.
Sensor Flex
NetPing 8/PWR-220 v4/SMS Terminal
First wire
One of IO lines – 1/2/3/4
Second wire
G
Important! Sensors of a dry contact type, a
, a leakage sensor, and others are plugged to IO lines of a device. You
supply voltage sensor
can plug any four sensors out of this set.
Important! A corresponding IO line should be set to an input mode in settings of a device.
Important! Sensors of a dry contact type, a
, a leakage sensor, and others are plugged to IO lines of a device. You
supply voltage sensor
can plug any four sensors out of this set.
Important! A corresponding IO line should be set to an input mode in settings of a device.