Страница 1: ...System Cabinets 42U 1280 mm System Cabinet Guide September 2018 215 12157_C0 doccomments netapp com ...
Страница 2: ......
Страница 3: ...nstalling equipment in the system cabinet 18 Powering on the system cabinet 19 Replacing PDUs 21 Reversing the system cabinet front door 22 Removing the illuminated badge 23 Removing the system cabinet door 24 Moving the badge power supply and cabling 24 Reversing the door hinge and lock catch 27 Reinstalling the door and illuminated badge 29 Reinstalling the system cabinet door 29 Reinstalling th...
Страница 4: ...d for cooling Common key This key unlocks the front doors rear doors and side panels Spares kit This kit is inside the system cabinet attached to the cabinet door It contains the following components Four 10 32 x 0 75 inch Phillips pilot screws Four 10 32 cage nuts One cage nut insertion tool Two master key copies Cable access Cable pass throughs are built into the top and bottom of the cabinet as...
Страница 5: ...stem cabinets with the side panels off Four M12x20 Torx 30 screws used in system cabinet with side panels on Eight M6x10 countersunk Torx 30 screws used in system cabinet with side panels off Support rail kit If you ordered additional support rails with your system cabinet each kit contains one left and one right support rail Attention The support rails and kit are designed to fit only the NetApp ...
Страница 6: ...at the intended location for the system cabinet is large enough for you to move the cabinet into place Required space for unpacking the system cabinet The following table defines the requires space needed to unpack and install your system cabinet Dimensions U S Metric Shipping ramp length 80 in 203 2 cm Clearance beyond the ramp for cabinet mobility 72 in 182 9 cm Shipping pallet depth 59 in 149 9...
Страница 7: ...ing illustrations show top and bottom views of the system cabinet and identify the openings through which you can run cable bundles from the floor of your data center into the system cabinet The illustrations also show the location of the system cabinet casters and leveling feet Caution To prevent your system cabinet from falling through the data center floor do not attempt to roll the system cabi...
Страница 8: ...enterline of Leveling Feet 968 cm Centerline of Casters 160 cm Cable Access 512 cm Cable Access REAR FRONT OPEN OPEN OPEN Supported PDU types and specifications The system cabinet supports different Power Distribution Unit PDU types The PDUs are compliant with NEMA or IEC The most current information for PDUs supported in your system cabinet is listed in the Hardware Universe hwu netapp com 8 42U ...
Страница 9: ...s x2 Unbuckle the straps and remove top outside bumpers 4 X straps and top bumpers not used with light load or empty cabinet shipments 3 Extra support bracket not used with light load or empty cabinet shipments 5 6 Attach ramp to pallet on side labeled UNLOAD align ramp end bolts with the holes on the pallet and lower it into place x2 front x2 rear x2 7 R e m o v e s i d e p a n e l s Rear Front 8...
Страница 10: ...nstalling the cabinet interconnect kit You can connect system cabinets together by using the optional cabinet interconnect kit It is recommended that you install the kit to prevent the cabinets from pulling apart and damaging system cables Steps 1 Place the system cabinets close together The cabinets should be arranged similarly to the following illustration with the cabinet with the controller mo...
Страница 11: ...at the top of the system cabinet frame b Gently push the side panel against the cabinet frame and then lock it in place with the key c Repeat these substeps for the remaining side panels 3 If you are installing the interconnect kit with the side panels removed remove the front door whose hinges are on the edge where the cabinets meet a Unlock and open the front door that is being removed b Use the...
Страница 12: ...Front 2 Back press 1 1 Illuminated bezel circuit board and cable 2 Back panel and thumbscrews c Use the following illustration for reference to remove the front door 12 42U 1280 mm System Cabinet Guide ...
Страница 13: ...f the hinge c Gently tip the top of the door away from the system cabinet frame and then release the hinge pin d Lift the door off the bottom hinge and then set the door aside 5 Move the system cabinets completely together and then align and level them by adjusting the four leveling feet at the bottom of the system cabinets 6 Install the interconnect brackets Use the following illustration for ref...
Страница 14: ...stic push in rivets on the system cabinet top 2 Top interconnect bracket 3 Bottom interconnect bracket Use the following illustration for reference if you are installing the interconnect brackets with the system cabinet side panels off 14 42U 1280 mm System Cabinet Guide ...
Страница 15: ... by installing the optional bolt down kit Installing the kit prevents the system cabinets from being rolled out of position Before you begin You must supply the appropriate anchor bolt for your floor for each bolt down bracket Steps 1 Mark the area on your floor where the system cabinet will be installed and then roll the cabinet into place Installing a system cabinet 15 ...
Страница 16: ...ets will be anchored to the floor and then drill the holes for the brackets 6 If the bolt down brackets are too low to align with the mount points on the system cabinet frame place a spacer bracket over the hole in the floor 7 Bolt the front brackets to the floor and then using the kit bolts bolt the brackets to the cabinet frame 8 Lower the leveling feet as needed and then tighten the rear bolt d...
Страница 17: ...lable space 2 Locate where you need to install the support rails and then install them using the following illustration for reference 1 2 5 10x32 screw Use with DS460C only Use with all other system chassis Repeat the steps for the opposite rail 4 Rear view Front view 10x32 screw 3 3 If your equipment mounting flanges extend beyond the screw holes in the support rail install cage nuts above the su...
Страница 18: ...torage controllers should be in the middle of the system cabinet The disk shelves should be above and below the storage controllers Any switches should be at the very top of the system cabinet Note If your equipment mounting flanges extend beyond the screw holes in the support rail install cage nuts above the support rail where needed to secure the equipment to the cabinet upright 3 Install blanki...
Страница 19: ...power circuits available for each PDU in your system cabinet Steps 1 Connect your equipment to the PDUs making sure that you connect each component s power supplies to a PDU on opposite sides of the system cabinet 2 Feed the PDU power cables through an opening in the system cabinet Use one of the following openings The top of the system cabinet Between the rear door bottom and frame of the system ...
Страница 20: ...power sources that are on separate AC circuits 5 Turn on the power switches or circuit breakers to the PDUs 6 Turn on the power to your components and then boot the system 7 Close and lock the system cabinet doors 20 42U 1280 mm System Cabinet Guide ...
Страница 21: ...upporting the replacement PDU align the slot on the mounting bracket of the PDU with the top holes of the frame on the inside of the system cabinet and then secure the PDU to the system cabinet frame using the mounting screws from the old PDU 7 Secure the bottom of the PDU to the system cabinet frame and then tighten all of the mounting screws 8 Verify that all of the power switches or circuit bre...
Страница 22: ... the opposite side of the front of the system cabinet frame Before you begin About this task You need the following tools and equipment to complete the door reversal for system cabinets with illuminated badges A Phillips screwdriver A 5 mm Allen wrench magnetic Allen wrench is recommended Needle nose pliers A step ladder so that you can easily access the Allen bolts in the top hinge 22 ...
Страница 23: ...n the captive screws on the badge back panel on the inside of the door and then gently pull the back panel away from the door mesh 3 Unplug the power cord from the back panel by pressing the locking clip on the plug unplugging the cord from the socket and removing the cable from the back panel Set the back panel aside 4 Carefully remove the screws from the back of the badge Note The stems on the t...
Страница 24: ...assembly from the system cabinet door and set it aside 7 Lift the top hinge pin until it clears the bottom of the hinge 8 Gently tip the top of the door away from the system cabinet frame and then release the hinge pin 9 Lift the door off the bottom hinge and set the door aside Moving the badge power supply and cabling You must move the power supply and illuminated badge cabling to the opposite si...
Страница 25: ... frame and then remove the power supply housing 3 Install the power supply and power supply housing on the opposite side of the system cabinet a Locate the two screw holes next to each other on the cabinet frame and then attach the top of the power supply housing to the bottom most of the two screw holes Note You might need to remove the bottom cable retention strap if present b Secure the bottom ...
Страница 26: ... clips from the retaining clips and then slide the conduit off the power cable Keep the retaining clips and screws for installing the conduit on the opposite side of the cabinet 5 Move the badge power cable to the other side of the cabinet 26 42U 1280 mm System Cabinet Guide ...
Страница 27: ...t frame to the back of the cabinet 6 Reinstall the cable conduit a Slide the conduit over the PDU power cable and route the conduit along the system cabinet frame to the PDU b Install the conduit retaining clips from the other side of the cabinet over the conduit to secure it to the cabinet frame 7 Plug the badge cable back into the power supply but do not reconnect the power supply to the power s...
Страница 28: ...the cabinet frame Spare Allen screws are provided in the spares kit that shipped with your system cabinet 2 Remove the screws securing the bottom hinge from the system cabinet frame and set the screws and hinge aside 4 5 1 2 3 1 Door grounding screw with grounding wire spade 2 Grounding wire 3 Frame grounding wire lug 4 Top front door hinge with hinge pin held by retaining clip 5 Lock catch 3 Reve...
Страница 29: ...the system cabinet upright Reinstalling the door and illuminated badge After you move the power supply and components to the other side of the system cabinet and moved the hinges and lock catch you must reinstall the system cabinet door and the illuminated badge and then reconnect the badge to the power source Reinstalling the system cabinet door After you reverse the door hinge and door catch you...
Страница 30: ...connect brackets Reinstalling the illuminated badge After the system cabinet door is installed you need to install the illuminated badge to complete the door reversal process and then close and lock the front door Steps 1 Using the following illustration for reference reinstall the illuminated badge on the front door of the system cabinet Front Back Back Front ALIGN EDGE TO TOP OF FRONT BADGE 1 2 ...
Страница 31: ...IN ANY WAY OUT OF THE USE OF THIS SOFTWARE EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE NetApp reserves the right to change any products described herein at any time and without notice NetApp assumes no responsibility or liability arising from the use of products described herein except as expressly agreed to in writing by NetApp The use or purchase of this product does not convey a license u...
Страница 32: ...APP the NETAPP logo and the marks listed on the NetApp Trademarks page are trademarks of NetApp Inc Other company and product names may be trademarks of their respective owners http www netapp com us legal netapptmlist aspx 32 ...
Страница 33: ...ing this document send us your comments by email doccomments netapp com To help us direct your comments to the correct division include in the subject line the product name version and operating system If you want to be notified automatically when production level documentation is released or important changes are made to existing production level documents follow Twitter account NetAppDoc You can...
Страница 34: ...ersing system cabinet door 27 I illuminated badge installing 29 removing 23 illuminated badge removal 23 information how to send feedback about improving documentation 33 installation required tools for 6 installing additional support rails 16 equipment in an empty system cabinet 18 illuminated badge 29 introduction to 10 interconnect kits connecting system cabinets together using 10 K kits featur...
Страница 35: ...oors reinstalling 29 system cabinets connecting with the interconnect kit 10 dimensions and space requirements 6 features for setting up and cabling 4 installing bolt down kit to secure 15 introduction to preparing to install 4 powering on 19 reversing door hinge and lock catch 27 unpacking 9 system components adding to prepopulated system cabinets 18 T tools required for installing 6 Twitter how ...