Ness R8
- Installation and Programming Manual
39
This option selects the miscellaneous alarms which will report
Restorals by dialler.
See P75E, page 38, for a list of Miscellaneous Alarms.
PROGRAMMING SEQUENCE
1. Press:
P77E
2. Press:
[1-8] E
to toggle each zone on or off.
Zone light/s on indicates which option/s is enabled.
PROGRAM MODE LEVEL:
Installer, Remote by PC.
FACTORY DEFAULT:
1–8 = ON, All Miscellaneous
Alarms report Restorals.
RELATED OPTIONS:
P75E, Report Miscellaneous
Alarms.
P77E
REPORT MISCELLANEOUS RESTORALS
PROGRAMMING
Zones selected to Report Multiple Zone Alarms will report each
time the zone alarms. The number of reports is a maximum of 15.
Zones not selected will report only once, until reset by an opening
or a valid code.
PROGRAMMING SEQUENCE
1. Press:
P78E
2. Press:
[1-8] E
to toggle each zone on or off.
Zone light/s on indicates which option/s is enabled.
PROGRAM MODE LEVEL:
Installer, Remote by PC.
FACTORY DEFAULT:
1–8 = ON, All zones report
Multiple Zone Alarms.
RELATED OPTIONS:
P74E, Report Zone Alarms.
P78E
REPORT MULTIPLE ZONE ALARMS
This option selects when the dialler sends Zone Restoral Reports.
Only one of the following options may be selected.
Restoral reporting options also apply to 24hr zones.
P82E 1E: Send Restoral immediately when resealed.
P82E 2E: Send Restoral after siren time & resealed.
P82E 3E: Send Restoral on Disarm & resealed.
P82E 4E: Send Restoral on Disarm always.
PROGRAMMING SEQUENCE
1. Press:
P82E
2. Press:
[1-4] E
to toggle each option on or off.
Zone light/s on indicates which option is enabled.
PROGRAM MODE LEVEL:
Installer, Remote by PC.
FACTORY DEFAULT:
4E = ON, Send Restoral on
Disarm always.
RELATED OPTIONS:
P74E, Report Zone Alarms.
P82E
RESTORAL REPORTING OPTIONS