Mounting the UPS
Wall Mounting
The UPS’s maximum input current is read off the UPS’s nameplate. For
example, if the nameplate gives the maximum input current as 20A,
the circuit breaker should be rated at least 25A.
Using the case as a template, secure the case to the wall with the four
Phillips-head wood screws supplied with the unit.
Figure 50 – Wall Mounting
Pole Mounting
The Novus Micro Secure can be pole mounted with the optional
mounting bracket (Alpha Kit# 740-751-21). It allows you to mount to
either a vertical or horizontal, steel, concrete, or wooden pole.
Steel or Concrete Pole Mounting
To strap mount the UPS to the pole, you need the optional mounting
bracket and two ½-inch straps (Band-It #C20499 straps, #C00369 Tool
and #C25499 Buckle or equivalent).
1. Attach the straps to the mounting bracket.
2. Attach the bracket to the pole.
3. Secure the UPS enclosure to the mounting bracket with the two
mounting screws and two nuts provided with the kit.
Figure 51 – Steel or Concrete Pole Mounting
R450 Data Collector Installation and Maintenance Guide
57
Chapter 4: I Uninterruptible Power Supply
Содержание R450
Страница 2: ......
Страница 3: ...R450 Data Collector Installation and Maintenance Guide ...
Страница 8: ...This page intentionally left blank ...
Страница 18: ...This page intentionally left blank xvi R450 Data Collector Installation and Maintenance Guide Tables ...
Страница 20: ...This page intentionally left blank xviii R450 Data Collector Installation and Maintenance Guide Tables ...
Страница 143: ......