ENGLISH - 4/8
MI004530-E
t
AN
ALOG
INPUTS
DIGIT
AL
POWER SUPPLY
RELAIS
DIGITAL
OUTPUTS
IDC10
RS485
RJ45
ANT.
RS232
USB
1500 V
A
3000 V
A
4
2
3
10 11 12
24
19
6
5
...
...
13
18
STANDARDS
EN61000-6-4
Electromagnetic emission, industrial environment.
EN61000-6-2
Electromagnetic immunity, industrial environment.
.
EN301 511
Harmonized standard for mobile stations
.
EN301 489-1
ElectroMagnetic Compatibility for radio equipment
.
EN301 489-7
Specific (EMC) conditions for mobile radio equipment
EN60950
Safety of information Technology Equipment.
INSULATION
ENVIRONMENTAL
CONDITIONS
Temperature
Humidity
Storage temperature
Protection rating
-10 + 50°C / (-10 + 40°C with internal UPS use).
–
–
30% –
t
ing.
90% no condens
–
–
-20 + 65°C / (-20 + 45°C < 6
with internal UPS use).
months
IP20.
MOUNTING
35mm IEC EN60715 DIN Rail.
INTERNAL UPS
Backup
. Duration: up to 1 hour.
rechargeable batteries
CONNECTIONS
Removable three pole screw terminal pitch 5mm, for cable up to 2.5 mm ,
2
rear IDC10, front RJ45, Micro USB and Antenna SMA.
POWERSUPPLY
Voltage
Power absorbed
11 – 40 V
or 19 – 28 V
–
.
~
~
50
60 Hz
< 6.5W.
DIGITAL INPUTS
Number of channels 4. PNP or NPN configurable.
Input voltage OFF<4V ON>8V (Max. 24V ). Input current 20mA.
C
Max. frequency 30Hz. Absorbed Current 3mA at 12V
10mA at 24V .
C
C
TOTALIZERS
32 bit totalizers 4x on non-volatile memory.
COUNTERS
32 bit resettable counters 4x on non-volatile memory.
DIGITAL OUTPUTS
Number of channels
SPDT Relays with free contacts.
2.
Max. Voltage 250V . Max. Current 2A.
A
ANALOG INPUTS
Number of channels 2. mA
or V
configurable.
C
C
Voltage input 0 – 30V. accuracy 0.1% of the Full Scale.
Current input 0 20mA
–
accuracy 0.1% of the Full Scale.
Inputs protection 40V / 25mA. Resolution 16 bit.
COMMUNICATION
PORTS
Rear RS485 COM1 port. RS485 or RS232 M10-M11-M12 COM2 screw
terminals port. Ethernet 10/100 baseT RJ45 frontal port with autoswitch.
MicroUSB side port.
TECHNICAL SPECIFICATIONS
ENGLISH - 3/8
MI004530-E
t
LED
Status
LED’s meaning
DI1
(Red)
ON (NPN)
Digital Input 1: Energized (
closed contact
GND
)
ON (PNP)
Digital Input 1: Energized (
closed contact
+12V
)
OFF
Digital Input 1: De-energized (open contact)
DI2
(Red)
ON (NPN)
Digital Input : Energized (
closed contact
2
GND
)
ON (PNP)
Digital Input : Energized (
closed contact
2
+12V
)
OFF
Digital Input : De-energized (open contact)
2
DI3
(Red)
ON (NPN)
Digital Input : Energized (
closed contact
3
GND
)
ON (PNP)
Digital Input : Energized (
closed contact
3
+12V
)
OFF
Digital Input : De-energized (open contact)
3
DI4
(Red)
ON (NPN)
Digital Input : Energized (
closed contact
4
GND
)
ON (PNP)
Digital Input : Energized (
closed contact
4
+12V
)
OFF
Digital Input : De-energized (open contact)
4
PWR/STS
(Green)
ON
n
Z-UMTS ON inactive log (status=ready)
Slow Blinking
2.8 sec ON 0.4 sec OFF
nnnnnnnnnnnnnnoo
Z-UMTS active log (status=normal)
Slow Blinking
1.6 sec ON 1.6 sec OFF
nnnnnnnnoooooooo
Battery powered inactive log (status=battery backup)
Medium Blinking
0.8 sec ON 0.8 sec OFF
nnnnoooonnnnoooo
Low battery warning
Fast Blinking
0.2 sec ON 0.2 sec OFF
nononononononono
Z-UMTS initializing or shutdown
Fast Blinking
0.6 sec
1 sec OFF
non
nonooooononooooo
Error, please refer to the diagnostic
OFF
o
Z-UMTS OFF
SD/STS
(Red)
ON
n
SD card mounted in the right way
Medium Blinking
0.8 sec ON 0.8 sec OFF
nnnnoooonnnnoooo
SD card activity
Fast Blinking
0.2 sec ON 0.2 sec OFF
nononononononono
SD card error
OFF
o
SD card not present
ETH LNK
(Green)
Blinking
RJ45 connection activated
ETH TRF
(Yellow)
Blinking
Traffic on Ethernet port
LED SIGNALING ON FRONT PANEL
ENGLISH - 2/8
MI004530-E
t
LED
Status
LED’s meaning
DO1
(Red)
ON
Digital output 1, relay energized
OFF
Digital output 1, relay de-energized
DO2
(Red)
ON
Digital output , relay energized
2
OFF
Digital output , relay de-energized
2
485 ACT
(Green)
Slow Blinking
2.8s ON
0.4s OFF
n
o
nnnnnnnnnnnnnnoo
RS485 activity or RS232 activity
OFF
o
RS485 or RS232 serial interface not used
Fast Blinking
0.2s ON
0.2s OFF
n
o
nononononononono
RS485 or RS232 communication Timeout
GSM
(Yellow)
ON
n
nnnnnnnnnnnnnnnnnnnn
HSDPA / HSUPA / HSPA+ / DC-HSPA Mode
Blinking
1.9s ON
0.1s OFF
n
o
nnnnnnnnnnnnnnnnnnno
WCDMA Mode
Blinking
1.7s ON
0.3s
n
ono
nnnnnnnnnnnnnnnnnono
GSM / GPRS / EDGE Mode
Fast Blinking
0.1s ON
0.1s OFF
n
o
nononononononononono
N
or Missing Signal
etwork Searching
OFF
o
Modem OFF
LED SIGNALING ON FRONT PANEL
Dimensions (L×H×W)
35 x 100 x 111 mm (with terminals).
Weight
250 g.
Case
Material PA6, black color.
100 mm
Z-UMTS
Connector
Rear bus
ETHERNET
micro
USB
Analog
IN 1, 2
6
5
4
RS485/RS232
COM2 (SW2)
15
14
13
Digital
IN 1, 2
Relay
OUT 1
18
17
16
Digital
IN 3, 4
Relay
OUT 2
10
11
12
19
20
21
22
23
24
Power
supply
3
2
1
MADE IN IT
AL
Y
ET005040B
HSP
A+ unit - RTU
multiprotocol datalogger
Power Supply
1
1
–
40 V
~
19
–
28 V (50
–
60Hz)
~
Max 6.5 W
micro
SD Card
SIM
CARD
RS485 COM1 and
Power Supply
1
1
1 mm
1112
10
20 21
19
2324
22
35 mm
19 2021
22 23 24
13 1415
DI4
DI3
DI2
DI1
1 2 3
4 5 6
10 11 12
SENECA
ETH
TRF
ETH
LNK
PWR/
STS
SD/
STS
16 17 18
DO2
DO1
S
485
ACT
ETHERNET
ANTENNA
Z-UMTS
micro
USB
MODULE LAYOUT
ENGLISH - 1/8
ENGLISH LANGUAGE INSTRUCTIONS
MI004530-E
This document is property of SENECA rl. Duplication and reproduction are forbidden, if not authorized.
S
Contents of the present documentation refers to products and technologies described in it.
This informations may be modified or integrated for technical and / or commercial requirements.
SENECA s.r.l.
Headquarters: Via Austria, 26 – 35127 – PADOVA – ITALY
Phone +39.049.8705355 - 8705359 - Fax +39.049.8706287
Manuals and configuration software are available at website:
www.seneca.it/products/z-umts
EN
EN
Datalogger HSPA + with built-in I/O, telecontrol functions,
embedded UPS and advanced programming language
Z-UMTS