 Universal Wall-Mount Controller 

Modbus Communication Module User Guide

 

 

www.neptronic.com 

page | 5 

Register 

Index 

Description 

Data Type 

Range 

Writable 

400

20

 

Binary input statuses of 2 binary inputs. 

Bit String 

[B2-B15]

Reserved 

 

B0: Binary Input 1

  

0 = Open, 1 = Close 

 
B1: Binary Input 2 

0 = Open, 1 = Close 

RO 

400

21

 

Actual system occupancy state. 

Unsigned 

1 = NoOccupancy, 2 = Occupancy, 3 = Override 

RO 

400

22

 

Actual night setback state of the system. 

Unsigned 

1 = Day, 2 = Night, 3 = Override 

RO 

400

23

 

Actual heating demand of ramp 1. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

24

 

Actual heating demand of ramp 2. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

25

 

Actual cooling demand of ramp 1. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

26

 

Actual cooling demand of ramp 2. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

27

 

Actual changeover demand. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

28

 

Actual fan demand. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

29

 

Actual dehumidification demand. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

30

 

Actual humidification demand. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

RO 

400

31

 

CL_HT_SwitchTimerCount - countdown until the system is 
able to swap the demand. 

Unsigned 

Scale 1

 

Unit: Seconds, Range: 0 to 7200 seconds, 

Value/1 (e.g. 100 secs = 100)

 

RO 

400

32

 

Analog output 1 value. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

400

33

 

Analog output 2 value. 

Unsigned 

Scale 10

 

Unit: %, Range: 0% to 100%, 

Value x 10 (e.g. 100% = 1000)

 

 

 

 

 

 

 

Содержание TUCB Series

Страница 1: ...Wall Mount Controller TUCB TUHB Series Modbus Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humidity S...

Страница 2: ...s The controller Modbus server supports the following exception codes o Illegal data address o Illegal data value o Slave device busy Serial Line The controller Modbus over serial line uses RTU transm...

Страница 3: ...Unsigned Scale 100 0 9600 19200 38400 or 57600 0 Auto Baud Rate Detection Value 100 e g 38400 baud 384 W 40002 Communication port configuration Unsigned 1 No parity 2 Stop bits 2 Even parity 1 stop bi...

Страница 4: ...3 Changeover temperature sensor reading Signed Scale 100 Unit C F Range 40 C to 100 C or 40 F to 212 F Value x 100 e g 23 C 2300 or 33 F 3300 RO 40014 Control temperature reading Signed Scale 100 Unit...

Страница 5: ...Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40026 Actual cooling demand of ramp 2 Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40027 Actual changeover demand U...

Страница 6: ...f 1 On B3 Cfg_HeatingRamp1Lock 0 Off 1 On B4 Cfg_HeatingRamp2Lock 0 Off 1 On B5 Cfg_ChangeOverRampLock 0 Off 1 On B7 Cfg_HumidifyRampLock 0 Off 1 On B8 Cfg_DehumidifyRampLock 0 Off 1 On W 40036 System...

Страница 7: ...tPointLock 0 Off 1 On B4 Cfg_ProgramModeLock 0 Off 1 On B7 AL_FreezeProtection 0 Off 1 On B8 Cfg_UserSysOffModes 0 Enable 1 Disable B9 Cfg_KeyPadBottomLeftLock 0 Off 1 On B10 Cfg_KeyPadUpperLeftLock 0...

Страница 8: ...Output2Direction 0 Direct 1 Reverse B8 Cfg_BinaryOutput3Direction 0 Direct 1 Reverse B9 Cfg_BinaryOutput4Direction 0 Direct 1 Reverse B10 Cfg_BinaryOutput5Direction 0 Direct 1 Reverse B11 Cfg_BinaryOu...

Страница 9: ...0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or 2 F 20 W 40051 Heating proportional band for ramp 2 Unsigned Scale 10 Unit depends on system unit 0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or...

Страница 10: ...d Scale 1 Unit Minutes Range 0 to 15 minutes Value x 1 e g 10 mins 10 W 40067 NSB override delay in minutes Unsigned Scale 1 Unit Minutes Range 0 to 180 minutes Value x 1 e g 100 mins 100 W 40068 Unoc...

Страница 11: ...ch binary input 16 OverHeat binary input 17 Selector switch binary input 18 Humidity sensor 0 10V W 40079 External temperature sensor offset correction Signed Scale 100 Unit depends on system unit Ran...

Страница 12: ...3 V 30 W 40092 Position of CH1 AO output while heating Unsigned Scale 1 Unit Range 0 to 100 Value x 1 e g 10 10 W 40093 Ramp to control binary output 1 Unsigned 1 Off 2 Changeover with fan 3 Cooling...

Страница 13: ...on percentage for contact BO3 Unsigned Scale 1 Unit Range 0 to BO3closepos 4 Value x 1 e g 20 20 W 40105 Ramp to control binary output 4 Unsigned 1 Off 2 Changeover with fan 3 Cooling 1 with fan 4 Coo...

Страница 14: ...s Value x 1 e g 5 5 mins W 40115 Close position percentage for contact BO6 Unsigned Scale 1 Unit Range 15 to 80 Value x 1 e g 20 20 W 40116 Open position percentage for contact BO6 Unsigned Scale 1 Un...

Страница 15: ...pancy or day mode Unsigned Scale 10 Unit RH Limited by min max humidity setpoint Value x 10 e g 20 RH 200 W 40126 Dehumidification setpoint RH in unoccupied or night mode Unsigned Scale 10 Unit RH Ran...

Страница 16: ...le 40135 Minimum output voltage required for cooling for the 6 way valve Unsigned Scale 100 Unit V Range 0 to 11 V Value x 100 e g 2V 200 W 40136 Minimum output voltage required for heating for the 6...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...eau blvd Montreal Qc H4N 1R6 Canada neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Easter...

Отзывы: