Universal Wall-Mount Controller
Modbus Communication Module User Guide
www.neptronic.com
page | 9
Register
Index
Description
Data Type
Range
Writable
400
43
Display information.
Unsigned
1 = Temperature and Demand, 2 = Setpoint and Demand, 3 = Temperature Only,
4 = Setpoint Only, 5 = Off
W
400
44
Temperature control source.
Unsigned
1 = Network Temp, 2 = Intern Temp, 3 = Extern Temp
W
400
45
Network fallback timeout.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 60,
Value/1 (e.g. 30 mins = 30)
W
400
46
Minimum occupancy/day setpoint.
Signed
Scale 10
Unit: ºC/ºF, Range: 10ºC to max or 50ºF to max
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
W
400
47
Maximum occupancy/day setpoint.
Signed
Scale 10
Unit: ºC/ºF, Range: min to 40ºC or min to 104ºF
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
W
400
48
Cooling temperature setpoint in unoccupied or night mode.
Signed
Scale 10
Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g.18°C = 180 or 60ºF = 600)
W
400
49
Heating temperature setpoint in unoccupied or night mode.
Signed
Scale 10
Unit: ºC/ºF, Range: 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g. 18°C = 180 or 60ºF = 600)
W
400
50
Heating proportional band for ramp 1.
Unsigned
Scale 10
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9Fº
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
51
Heating proportional band for ramp 2.
Unsigned
Scale 10
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9Fº
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
52
Cooling proportional band for ramp 1.
Unsigned
Scale 10
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
53
Cooling proportional band for ramp 2.
Unsigned
Scale 10
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
54
Changeover proportional band.
Unsigned
Scale 10
Unit: depends on system unit, 0.5ºC to 5ºC or 1ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
55
Heating deadband for ramp 1.
Unsigned
Scale 10
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
56
Heating deadband for ramp 2.
Unsigned
Scale 10
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
57
Cooling deadband for ramp 1.
Unsigned
Scale 10
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
58
Cooling deadband for ramp 2.
Unsigned
Scale 10
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W
400
59
Changeover deadband.
Unsigned
Scale 10
Unit: depends on system unit, 0ºC to 5ºC or 0ºF to 9ºF
Value x 10 (e.g. 1
ºC
= 10 or 2ºF = 20)
W