Universal Wall-Mount Controller
Modbus Communication Module User Guide
www.neptronic.com
page | 10
Register
Index
Description
Data Type
Range
Writable
400
60
Changeover setpoint.
Signed
Scale 10
Unit: depends on system unit, 10ºC to 40ºC or 50ºF to 104ºF
Value x 10 (e.g. 12ºC = 120 or 60ºF = 600)
W
400
61
Fan time out in seconds.
Unsigned
Scale 1
Unit: Seconds, Range: 0 to 255 seconds,
Value x 1 (e.g.100 secs = 100)
W
400
62
Fan damping factor in seconds.
Unsigned
Scale 1
Unit: Seconds, Range: 0 to 255 seconds,
Value x 1 (e.g.100 secs = 100)
W
400
63
Heating integral time factor in seconds.
Unsigned
Scale 1
Unit: Seconds, Range: 0 to 250 seconds,
Value x 1 (e.g.100 secs = 100)
W
400
64
Cooling integral time factor in seconds.
Unsigned
Scale 1
Unit: Seconds, Range: 0 to 250 seconds,
Value x 1 (e.g.100 secs = 100)
W
400
65
CL_HT_SwitchTimer - Delay between cool and heat or vice
versa.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 120 minutes,
Value x 1 (e.g.100 mins = 100)
W
400
66
Cooling anticycle delay in minutes.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 15 minutes,
Value x 1 (e.g.10 mins = 10)
W
400
67
NSB override delay in minutes.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 180 minutes,
Value x 1 (e.g.100 mins = 100)
W
400
68
Unoccupied override delay in minutes.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 180 minutes,
Value x 1 (e.g.100 mins = 100)
W
400
69
Occupancy minimum time in minutes.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 240 minutes,
Value x 1 (e.g.100 mins = 100)
W
400
70
Unoccupied override delay count down in minutes.
Unsigned
Scale 1
Unit: Minutes, Range: 0 to 180 minutes,
Value x 1 (e.g.100 mins = 100)
W
400
71
Fan mode (speed) in unoccupied or NSB mode.
Unsigned
1 = Low, 2 = Med, 3 = High, 4 = Auto
W
400
72
Fan mode (speed) when window is opened (alarm).
Unsigned
1 = Low, 2 = Med, 3 = High, 4 = Auto
W
400
73
Fan mode (speed) when door is opened (alarm).
Unsigned
1 = Low, 2 = Med, 3 = High, 4 = Auto
W
400
74
System control mode.
Unsigned
1 = Auto, 2 = Heat, 3 = Cool, 4 = Heat or Cool, 5 = Auto Lock
W
400
75
Override System occupancy/NSB mode.
Unsigned
1 = Locally, 2 = OFF, 3 = Occupied, 4 = Unoccupied, 5 = Day, 6 = Night
W
400
76
Internal temperature sensor offset correction.
Signed
Scale 100
Unit: depends on system unit, Range: ± 5ºC or +/-9ºF
Value x 100 (e.g.2ºC = 200 or 3ºF = 300)
W