 Universal Wall-Mount Controller 

Modbus Communication Module User Guide

 

 

www.neptronic.com 

page | 15 

Register 

Index 

Description 

Data Type 

Range 

Writable 

40

120

 

Configuration of binary input 2 mode. 

Unsigned 

1 = OFF 
2 = Override 
3 = Window 
4 = Door 
5 = DirtyFilter 
6 = FlowSwitch 

7 = OverHeat 
8 = SelectorSwitch (warning, must be used with 
FlowSwitch, in local mode Fan stay off) 
9 = Change over normally cool 
10 = Change over normally heat 
11 = NSB 
12 = Occupancy 

40

121

 

Delay before activation of BI2 in seconds. 

Unsigned 

Scale 1

 

Unit: Seconds, Range: 0 to 3600 seconds, 

Value x 1 (e.g. 20 secs = 20)

 

40

122

 

Delay before activation of AI1 in seconds. 

Unsigned 

Scale 1

 

Unit: Seconds, Range: 0 to 3600 seconds, 

Value x 1 (e.g. 20 secs = 20)

 

40

123

 

Delay before activation of AI2 in seconds. 

Unsigned 

Scale 1

 

Unit: Seconds, Range: 0 to 3600 seconds, 

Value x 1 (e.g. 20 secs = 20)

 

40

124

 

Humidity control mode status. 

Unsigned 

1 = Auto, 2 = Dehumidification, 3 = Humidification, 4 = Off 

40

125

 

Humidity setpoint (%RH) in occupancy or day mode. 

Unsigned 

Scale 10

 

Unit: %RH, Limited by min/max humidity setpoint, 

Value x 10 (e.g. 20%RH = 200)

 

40

126

 

Dehumidification setpoint (%RH) in unoccupied or night 
mode. 

Unsigned 

Scale 10

 

Unit: %RH, Range: 10%RH to 65%RH, 

Value x 10 (e.g. 20%RH = 200)

 

40

127

 

Humidification setpoint (%RH) in unoccupied or night 
mode. 

Unsigned 

Scale 10

 

Unit: %RH, Range: 10%RH to 65%RH, 

Value x 10 (e.g. 20%RH = 200)

 

40

128

 

Minimum user setpoint. 

Unsigned 

Scale 10

 

Unit: %RH, Range: 10%RH to max, 

Value x 10 (e.g. 20%RH = 200)

 

40

129

 

Maximum user setpoint. 

Unsigned 

Scale 10

 

Unit: %RH, Range: min to 90%RH, 

Value x 10 (e.g. 20%RH = 200)

 

40

130

 

Humidity proportional band. 

Unsigned 

Scale 10

 

Unit: %RH, Range: 3%RH to 10%RH, 

Value x 10 (e.g. 4%RH = 40)

 

40

131

 

Humidity deadband. 

Unsigned  

Scale 10

 

Unit: %RH, Range: 0%RH to 5%RH, 

Value x 10 (e.g. 4%RH = 40)

 

40

132

 

Internal humidity sensor offset correction. 
Only available on model TUHB24C6X2. 

Signed  

Scale 10

 

Unit: %RH, Range: ± 5%RH, 

Value x 10 (e.g. 2%RH = 20)

 

40

133

 

External humidity sensor offset correction.

 

 

Signed  

Scale 10

 

Unit: %RH, Range: ± 5%RH, 

Value x 10 (e.g. 2%RH = 20)

 

40

134

 

Voltage required for closing the 6-way valve. 

Unsigned 

Scale 100

 

Unit: V, Range: 0 to 11 V, 

Value x 100 (e.g. 2V = 200)

 

Содержание TUCB Series

Страница 1: ...Wall Mount Controller TUCB TUHB Series Modbus Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humidity S...

Страница 2: ...s The controller Modbus server supports the following exception codes o Illegal data address o Illegal data value o Slave device busy Serial Line The controller Modbus over serial line uses RTU transm...

Страница 3: ...Unsigned Scale 100 0 9600 19200 38400 or 57600 0 Auto Baud Rate Detection Value 100 e g 38400 baud 384 W 40002 Communication port configuration Unsigned 1 No parity 2 Stop bits 2 Even parity 1 stop bi...

Страница 4: ...3 Changeover temperature sensor reading Signed Scale 100 Unit C F Range 40 C to 100 C or 40 F to 212 F Value x 100 e g 23 C 2300 or 33 F 3300 RO 40014 Control temperature reading Signed Scale 100 Unit...

Страница 5: ...Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40026 Actual cooling demand of ramp 2 Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40027 Actual changeover demand U...

Страница 6: ...f 1 On B3 Cfg_HeatingRamp1Lock 0 Off 1 On B4 Cfg_HeatingRamp2Lock 0 Off 1 On B5 Cfg_ChangeOverRampLock 0 Off 1 On B7 Cfg_HumidifyRampLock 0 Off 1 On B8 Cfg_DehumidifyRampLock 0 Off 1 On W 40036 System...

Страница 7: ...tPointLock 0 Off 1 On B4 Cfg_ProgramModeLock 0 Off 1 On B7 AL_FreezeProtection 0 Off 1 On B8 Cfg_UserSysOffModes 0 Enable 1 Disable B9 Cfg_KeyPadBottomLeftLock 0 Off 1 On B10 Cfg_KeyPadUpperLeftLock 0...

Страница 8: ...Output2Direction 0 Direct 1 Reverse B8 Cfg_BinaryOutput3Direction 0 Direct 1 Reverse B9 Cfg_BinaryOutput4Direction 0 Direct 1 Reverse B10 Cfg_BinaryOutput5Direction 0 Direct 1 Reverse B11 Cfg_BinaryOu...

Страница 9: ...0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or 2 F 20 W 40051 Heating proportional band for ramp 2 Unsigned Scale 10 Unit depends on system unit 0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or...

Страница 10: ...d Scale 1 Unit Minutes Range 0 to 15 minutes Value x 1 e g 10 mins 10 W 40067 NSB override delay in minutes Unsigned Scale 1 Unit Minutes Range 0 to 180 minutes Value x 1 e g 100 mins 100 W 40068 Unoc...

Страница 11: ...ch binary input 16 OverHeat binary input 17 Selector switch binary input 18 Humidity sensor 0 10V W 40079 External temperature sensor offset correction Signed Scale 100 Unit depends on system unit Ran...

Страница 12: ...3 V 30 W 40092 Position of CH1 AO output while heating Unsigned Scale 1 Unit Range 0 to 100 Value x 1 e g 10 10 W 40093 Ramp to control binary output 1 Unsigned 1 Off 2 Changeover with fan 3 Cooling...

Страница 13: ...on percentage for contact BO3 Unsigned Scale 1 Unit Range 0 to BO3closepos 4 Value x 1 e g 20 20 W 40105 Ramp to control binary output 4 Unsigned 1 Off 2 Changeover with fan 3 Cooling 1 with fan 4 Coo...

Страница 14: ...s Value x 1 e g 5 5 mins W 40115 Close position percentage for contact BO6 Unsigned Scale 1 Unit Range 15 to 80 Value x 1 e g 20 20 W 40116 Open position percentage for contact BO6 Unsigned Scale 1 Un...

Страница 15: ...pancy or day mode Unsigned Scale 10 Unit RH Limited by min max humidity setpoint Value x 10 e g 20 RH 200 W 40126 Dehumidification setpoint RH in unoccupied or night mode Unsigned Scale 10 Unit RH Ran...

Страница 16: ...le 40135 Minimum output voltage required for cooling for the 6 way valve Unsigned Scale 100 Unit V Range 0 to 11 V Value x 100 e g 2V 200 W 40136 Minimum output voltage required for heating for the 6...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...eau blvd Montreal Qc H4N 1R6 Canada neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Easter...

Отзывы: