 Universal Wall-Mount Controller 

Modbus Communication Module User Guide

 

 

www.neptronic.com 

page | 4 

Register 

Index 

Description 

Data Type 

Range 

Writable 

400

10

 

System Status 2. 

Bit String 

[B1, B3-B6, B14]

Reserved 

 

B0: Selector Switch Status 
0 = Remote Mode, 1 = Local Mode 

 

B2: CO2 Alarm  
0 = Normal, 1 = Alarm 
 
B7: AL_Override  
0 = Off, 1 = On 
 
B8: AL_WindowOpened  
0 = Off, 1 = On 
 
B9: AL_DoorOpened  
0 = Off, 1 = On 

 

B10: AL_BI1 
0 = Off, 1 = On 

 

B11: AL_BI2 
0 = Off, 1 = On 
 
B12: AL_AI1  
0 = Off, 1 = On 

 

B13: AL_AI2  
0 = Off, 1 = On 
 
B15: AL_OverHeat 
0 = Off, 1 = On 

RO 

400

11

 

Internal temperature sensor reading. 

Signed 

Scale 100 

Unit: ºC/ºF, Range: 0ºC to 50ºC or 32ºF to 122ºF 

Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

 

RO 

400

12

 

External temperature sensor reading. 

Signed 

Scale 100 

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF 

Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

 

RO 

400

13

 

Changeover temperature sensor reading. 

Signed 

Scale 100 

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF 

Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

 

RO 

400

14

 

Control temperature reading. 

Signed 

Scale 100

 

Unit: ºC/ºF, Range: -40ºC to 100ºC or -40ºF to 212ºF 

Value x 100 (e.g. 23°C = 2300 or 33ºF = 3300)

 

400

15

 

Internal humidity sensor reading.

 

Only available on model TUHB24C6X2. 

Unsigned 

Scale 10

 

Unit: % RH, Range: 5%RH to 100%RH, 

Value x 10 (e.g. 30%RH = 300)

 

RO 

400

16

 

External humidity sensor reading. 

Unsigned 

Scale 10

 

Unit: % RH, Range: 5%RH to 100%RH, 

Value x 10 (e.g. 30%RH = 300)

 

RO 

400

17

 

Analog input 1 reading. 

Signed 

Scale 100

 

Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF,  
0 (open), 1 (close). 

Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)

 

RO 

400

18

 

Analog input 2 reading. 

Signed 

Scale 100

 

Unit: Volts or ºC/ºF, Range: 0V to 10V, -40 to 100ºC or -40 to 212ºF,  
0 (open), 1 (close). 

Value x 100 (e.g. 3 V = 300/18°C = 1800 or 33ºF = 3300)

 

RO 

400

19

 

CO2 sensor value in ppm. 

Signed 

Scale 1

 

Unit: ppm, 100 to 5000, 

Value x 1 (e.g. 500 ppm = 500)

 

RO 

Содержание TUCB Series

Страница 1: ...Wall Mount Controller TUCB TUHB Series Modbus Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humidity S...

Страница 2: ...s The controller Modbus server supports the following exception codes o Illegal data address o Illegal data value o Slave device busy Serial Line The controller Modbus over serial line uses RTU transm...

Страница 3: ...Unsigned Scale 100 0 9600 19200 38400 or 57600 0 Auto Baud Rate Detection Value 100 e g 38400 baud 384 W 40002 Communication port configuration Unsigned 1 No parity 2 Stop bits 2 Even parity 1 stop bi...

Страница 4: ...3 Changeover temperature sensor reading Signed Scale 100 Unit C F Range 40 C to 100 C or 40 F to 212 F Value x 100 e g 23 C 2300 or 33 F 3300 RO 40014 Control temperature reading Signed Scale 100 Unit...

Страница 5: ...Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40026 Actual cooling demand of ramp 2 Unsigned Scale 10 Unit Range 0 to 100 Value x 10 e g 100 1000 RO 40027 Actual changeover demand U...

Страница 6: ...f 1 On B3 Cfg_HeatingRamp1Lock 0 Off 1 On B4 Cfg_HeatingRamp2Lock 0 Off 1 On B5 Cfg_ChangeOverRampLock 0 Off 1 On B7 Cfg_HumidifyRampLock 0 Off 1 On B8 Cfg_DehumidifyRampLock 0 Off 1 On W 40036 System...

Страница 7: ...tPointLock 0 Off 1 On B4 Cfg_ProgramModeLock 0 Off 1 On B7 AL_FreezeProtection 0 Off 1 On B8 Cfg_UserSysOffModes 0 Enable 1 Disable B9 Cfg_KeyPadBottomLeftLock 0 Off 1 On B10 Cfg_KeyPadUpperLeftLock 0...

Страница 8: ...Output2Direction 0 Direct 1 Reverse B8 Cfg_BinaryOutput3Direction 0 Direct 1 Reverse B9 Cfg_BinaryOutput4Direction 0 Direct 1 Reverse B10 Cfg_BinaryOutput5Direction 0 Direct 1 Reverse B11 Cfg_BinaryOu...

Страница 9: ...0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or 2 F 20 W 40051 Heating proportional band for ramp 2 Unsigned Scale 10 Unit depends on system unit 0 5 C to 5 C or 1 F to 9F Value x 10 e g 1 C 10 or...

Страница 10: ...d Scale 1 Unit Minutes Range 0 to 15 minutes Value x 1 e g 10 mins 10 W 40067 NSB override delay in minutes Unsigned Scale 1 Unit Minutes Range 0 to 180 minutes Value x 1 e g 100 mins 100 W 40068 Unoc...

Страница 11: ...ch binary input 16 OverHeat binary input 17 Selector switch binary input 18 Humidity sensor 0 10V W 40079 External temperature sensor offset correction Signed Scale 100 Unit depends on system unit Ran...

Страница 12: ...3 V 30 W 40092 Position of CH1 AO output while heating Unsigned Scale 1 Unit Range 0 to 100 Value x 1 e g 10 10 W 40093 Ramp to control binary output 1 Unsigned 1 Off 2 Changeover with fan 3 Cooling...

Страница 13: ...on percentage for contact BO3 Unsigned Scale 1 Unit Range 0 to BO3closepos 4 Value x 1 e g 20 20 W 40105 Ramp to control binary output 4 Unsigned 1 Off 2 Changeover with fan 3 Cooling 1 with fan 4 Coo...

Страница 14: ...s Value x 1 e g 5 5 mins W 40115 Close position percentage for contact BO6 Unsigned Scale 1 Unit Range 15 to 80 Value x 1 e g 20 20 W 40116 Open position percentage for contact BO6 Unsigned Scale 1 Un...

Страница 15: ...pancy or day mode Unsigned Scale 10 Unit RH Limited by min max humidity setpoint Value x 10 e g 20 RH 200 W 40126 Dehumidification setpoint RH in unoccupied or night mode Unsigned Scale 10 Unit RH Ran...

Страница 16: ...le 40135 Minimum output voltage required for cooling for the 6 way valve Unsigned Scale 100 Unit V Range 0 to 11 V Value x 100 e g 2V 200 W 40136 Minimum output voltage required for heating for the 6...

Страница 17: ...Notes...

Страница 18: ......

Страница 19: ......

Страница 20: ...eau blvd Montreal Qc H4N 1R6 Canada neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Easter...

Отзывы: