SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 53
Problem
Possible Cause
Corrective Action
There is scale build-up on the
surface of the media panel
There is an excess concentration of
minerals and salts in the tank.
- Ensure that the water conductivity is
between 100 and 550 μS/cm and correct
it if necessary.
- Increase the dilution ratio using the
DilutionRatio
setting located in the
Installation
menu (
only for SKVF-R
models)
.
- Increase the water supply using the
WtrSupDutyCycle
setting located in the
Installation
menu, in order to drain more
water (only for
SKVF-D models
).
Water quality has changed.
Carry out a water quality test as per the
Water Sampling and Testing (Hygiene)
section
and ensure to follow the
Recirculation pump is not
functioning
(Only for SKVF-R models)
The SKVF is blocked by safety contacts
or an alarm.
Check that the safety contacts are not
open, in particular the high limit switch,
and that no alarms are present.
There is no demand.
Check that there is a demand for
humidity or temperature, otherwise setup
the system demand accordingly.
There is not enough water in the tank.
Check that the water level in the tank is
sufficient and that the fill pipe
connections are not being obstructed.
Evaporative cooler is operating
and the Status Display LED is
Red (ServiceDue setting
displays On)
The evaporative cooler is due for
servicing.
Service the evaporative cooler (see
Servicing and Maintenance section on
page 46).
Use
Request
setting in
Service
menu to
reset counters (see page 33).
Evaporative cooler is operating
and the Status Display LED is
Red (WtrServiceDue setting
displays On)
The 5μm pre-filter and silver ion
cartridges are due for replacement.
Replace the 5μm pre-filter and silver ion
cartridges. Use
Request
setting in
Service
menu to reset counters (see
page 33).
Evaporative cooler does not
operate (Screen turned Off,
Status Display LED: Blue)
The following components can be the
cause of this problem: float switch, PCB
or LCD display.
Call factory for troubleshooting
instructions.
Evaporative cooler is
cooling/humidifying (Screen
turned Off, Status Display
LED: Blue)
The display FFC cable is not connected
properly.
Verify that the connections of the FFC
cable are properly secured and are on
the correct side.
The LCD display is defective.
Replace the LCD display.