SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 35
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Control
RoomTempDemandLoop
[6]
Only appears if ControlProfile is set to an internal cool mode or
DemandSrc is set to TempRoomDemand.
PropGain:
28.5
min: 1.0, max: 200.0
Set the value of the room temperature demand proportional gain.
ITime:
15.0sec
min: 0.0sec, max: 900.0sec
Set the value of the room temperature demand integral time.
DTime:
0.0sec
min: 0.0sec, max: 60.0sec
Set the value of the room temperature demand derivative time.
ProbBand:
5.0%
min: 1.0%, max: 100.0%
Set the value of the room temperature demand proportional band.
TempSrc
:
None
None, RoomRH, Network, HRL
Select the reading source for the room temperature demand.
(Network option only applicable for models connected to BACnet or
Modbus.)
StptSrc
:
None
None, Internal, ControlInput
Select the room temperature demand setpoint source.
RHSupplyHLLoop
[6]
Only appears if ModHLProfile is set to an internal humidity mode or
HighLimitSrc is set to SupplyHLDemand.
PropGain:
28.5
min: 1.0, max: 200.0
Set the value of the supply high limit humidity demand proportional gain.
ITime:
15.0sec
min: 0.0sec, max: 900.0sec
Set the value of the supply high limit humidity demand integral time.
DTime:
0.0sec
min: 0.0sec, max: 60.0sec
Set the value of the supply high limit humidity demand derivative time.
ProbBand:
10.0%
min: 1.0%, max: 100.0%
Set the value of the supply high limit humidity demand proportional band.
RHSrc
:
None
None, SupplyHLRH, Network
Select the reading source for the supply high limit humidity demand.
(Network option only applicable for models connected to BACnet or
Modbus.)
StptSrc
:
None
None, Internal, ControlInput
Select the supply high limit humidity demand setpoint source.
TempSupplyHLLoop
[6]
Only appears if ModHLProfile is set to an internal cool mode or
HighLimitSrc is set to SupplyTempDemand.
PropGain:
28.5
min: 1.0, max: 200.0
Set the value of the supply high limit temperature demand proportional
gain.
ITime:
15.0sec
min: 0.0sec, max: 900.0sec
Set the value of the supply high limit temperature demand integral time.
DTime:
0.0sec
min: 0.0sec, max: 60.0sec
Set the value of the supply high limit temperature demand derivative
time.
ProbBand:
10.0%
min: 1.0%, max: 100.0%
Set the value of the supply high limit temperature demand proportional
band.
TempSrc
:
None
None, SupplyHLRH, Network
Select the reading source for the supply high limit temperature demand.
(Network option only applicable for models connected to BACnet or
Modbus.)
StptSrc
:
None
None, Internal, ControlInput
Select the supply high limit temperature demand setpoint source.
UnitControl
[4]
NtwkTimeout:
900sec
min: 1sec, max: 900sec
Define the amount of time the evaporative cooler may attempt to connect
to the BACnet or Modbus network before it stops operating due to a
communication error.
(Only appears if ControlProfile or ModHLProfile are set to
InternNetwork or ExternNetwork.)
DemandSrc:
None
None, ControlInput, HumRoomDemand, Network,
TempRoomDemand
Select the control demand source for the evaporative cooler.
(Network option only applicable for models connected to BACnet or
Modbus.)
HighLimitSrc:
None
None, ControlInput, SupplyHLDemand, Network,
SupplyTempDemand
Select the control high limit source for the evaporative cooler.
(Network option only applicable for models connected to BACnet or
Modbus.)
BinDemandSrc:
None
None, BinaryExtDemand
Select the demand source when in On/Off control mode.