SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 40
Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Network
ModbusServer
[1]
For models connected to Modbus.
Units:
Imperial
Metric, Imperial
Select whether to use a metric or imperial system of units for
the Modbus server.
ModbusRTU1In
[4]
Only appears if NtwrkOption is set to Modbus.
MAC:
1
min: 1, max: 247
Set the Modbus MAC address.
Autobaud:
Yes
No, Yes
Enable or disable automatic baud rate detection.
PortConfig:
No Parity, 2 Stop Bits
No Parity, 2 Stop Bits
Even Parity, 1 Stop bit
Odd Parity, 1 Stop bit
Select the Modbus communication port configuration.
BaudRate:
19200
9600, 14400, 19200, 38400, 57600
Select the baud rate for data transfer.
ModbusTCPIP0In [2]
For models connected to Modbus TCP/IP.
KeepAliveTimeOut:
5min
min: 1min, max: 1440min
Set the amount of time the communication stays open before
connection is cut out, when no signal is received from the
device.
ListeningPort:
502
min: 0, max: 65535
Set the communication port number.
Modbus TCP port number is set by default.
SMTP
[7]
SSL:
Off
Off, On
If turned to
On
, a secure socket layer will be used to encrypt the
communication between the device and the email server (Port
value must be set
to
587
and
Username
and
Password
settings
must be filled out). If turned to
Off
, the default socket will be
used (use Port
25
to use server without login account or Port
587
if login details for email account have been entered).
Port:
25
25, 587
If set to
25
, server to server email transfer is enabled (can only
be used if SSL is set to
Off)
. If set to
587
, client to server email
transfer is enabled.
ServerAddr:
192.168.100.100
Configure the server IP address for the email account.
From:
Current value
Set the email address that will be sending the evaporative
cooler notification messages.
To:
Current value
Set the email address that will be receiving the evaporative
cooler notification messages.
Username:
Current value
Set the login username for the email account.
Password:
Current value
Set the login password for the email account.
Notify
[3]
Alarm:
Off
Off, On
If turned to
On
, then the evaporative cooler alarm messages will
be sent to the email configured in the
SMTP
sub-menu.
Warning:
Off
Off, On
If turned to
On
, then the evaporative cooler warning messages
will be sent to the email configured in the
SMTP
sub-menu.
AppMsg:
Off
Off, On
If turned to
On
, then the evaporative cooler event messages will
be sent to the email configured in the
SMTP
sub-menu.
BACnetETH
[5]
For models connected to BACnet Ethernet.
RxValid:
0
*
Displays information on the received communication frames for
troubleshooting purposes.
RxInvalid:
0
*
RxLost:
0
*