SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 17
Electrical Connections
All work concerned with electrical installation MUST only be performed by a qualified electrician
and must conform to the procedure, regulation and local codes.
WARNING
:
Risk of electric shock. Isolate all power supplies before installation and maintenance of
the SKVF Evaporative cooler.
•
Use copper conductors only.
•
All incoming power supplies must be externally fused for over current protection.
•
The electrical supply must also be isolated for the purpose of emergency and servicing.
•
The isolator must have a contact separation of at least 1/8” (3 mm).
•
An external over current protection and disconnect circuit breaker must be installed on the supply, adjacent to the
unit.
•
Ensure that the size of the wire conductors is appropriate for the maximum current supplied.
•
Ensure that the incoming power cable is secured via a suitably sized cable gland.
•
Ensure that each terminal connection is secured firmly with a cable ferrule.
•
The SKVF evaporative cooler cabinet has an uninterrupted or unbroken electrical ground. Do not use the unit’s
frame to connect to ground.
Ground
L2
L1
or
(L)
(N)
Illustration 9 - Power Supply Connections
Electrical Power Supply
Table 6 - SKVF Electrical Power Supply
Model
Voltage (V)
Current (A)
SKVF-x15
120 - 1ph
3.0
208 - 1ph
1.8
230 to 240 - 1ph
1.5
SKVF-x30
120 - 1ph
5.8
208 - 1ph
3.4
230 to 240 - 1ph
2.9
SKVF-x60
120 - 1ph
10.8
208 - 1ph
6.3
230 to 240 - 1ph
5.4