SKVF Evaporative Cooler
Installation Instructions and User Manual
www.neptronic.com
Page | 14
Plumbing Connections
Plumbing Installation must conform to Local and National Codes.
Any installation work must be carried out by suitably qualified personnel.
Water Quality Guide
For normal operation of the
SKVF evaporative cooler
, Neptronic recommends connecting the SKVF to a clean and potable
source of water supply. Reverse osmosis (RO) water may be used for areas using hard water in order to minimise scale
build-up.
Reverse Osmosis Water
For SKVF evaporative coolers using RO water, Neptronic recommends operating the system within the following
parameters:
SKVF Type
Conductivity
Type R: Recirculation pump
> 100 μS/cm at 68°F (20°C)
Type D: Direct feed
> 150 μS/cm at 68°F (20°C)
The use of tanks and reservoirs using RO water is only permitted as part of a properly managed and hygiene monitored
water system and must be included as part of a water system risk assessment.
Controlled Substances
The supply water of the SKVF must be free of any toxic, carcinogenic and flammable substances, in order to avoid
contamination of the air passing through the media.
Refer to the table below for a list of substances that must not be found in the SKVF system.
Acrylamide
Antimony
Arsenic
Benzene
Benzo(a)pyrene
Boron
Bromate
Cadmium
Chromium
Clostridium perfringens (including
spores)
Cyanide
1,2-dichloroethane
Epichlorohydrin
Fluoride
Lead
Mercury
Nickel
Pesticides
Polycyclic aromatic hydrocarbons
Selenium
Tetrachloroethene and Trichloroethene
Trihalomethanes
Vinyl chloride
Water Monitoring
The water supply of the SKVF evaporative cooler must be monitored for hygiene as part of the maintenance program.
Refer to the Servicing and Maintenance section for further guidance.