Sub-Menu
Setting
Default
Range
(
* indicates no configuration; display only)
Description/Notes
Physical IO
Interlock:
Closed
* (Closed, Open)
Displays the status of the interlock.
If
Open
is displayed, it indicates that the evaporative cooler is
stopped as a result of the interlock safety being open.
BinExtDemand:
0%
* (0%, 100%)
Displays the demand value when in On/Off control mode.
(Only appears if BinDemandSrc is set to BinaryExtDemand.)
ControlInput:
Current value
* (min: 0%, max: 100%)
or
* (min: -40.0°F, max: 212.0°F)
* [min: -40.0°C, max: 100.0°C]
Units: C, F
Displays the current control input reading.
(Does not appear if ControlProfile is set to InternHumNetwork,
InternCoolNetwork, HRL Hum or HRL Cool.)
(Values are displayed in °C or °F when ControlProfile is set to
InternCoolAnalog.)
RoomRH:
Current value
* (min: 0%, max: 100%)
Displays the room humidity reading value.
(Only appears if ControlProfile is set to InternAnalog or RHSrc
is set to RoomRH.)
RoomTemp:
Current value
* (min: -40.0°F, max: 212.0°F)
* [min: -40.0°C, max: 100.0°C]
Units: C, F
Displays the room temperature reading value.
(Only appears if ControlProfile is set to InternCoolAnalog or
TempSrc is set to RoomTemp.)
SupplyHLRH:
Current value
* (min: 0%, max: 100%)
Displays the supply high limit humidity reading value.
(Only appears if ModHLProfile is set to InternAnalog or RHSrc
is set to SupplyHLRH.)
SupplyHLTemp:
Current value
* (min: -40.0°F, max: 212.0°F)
* [min: -40.0°C, max: 100.0°C]
Units: C, F
Displays the supply high limit temperature reading value.
(Only appears if ModHLProfile is set to InternCoolAnalog or
TempSrc is set to SupplyTemp.)
FanFeedBack:
Current value
* (min: 0Hz, max: 30000Hz)
Displays the feedback value from the ECM fan.
FanFeedBack2:
Current value
* (min: 0Hz, max: 30000Hz)
Displays the feedback value from the second ECM fan.
(Only applicable for SKVF-x60 models.)
FloatSwitch:
Current value
* (Inactive, Active)
Displays the status of the float switch.
(Only appears for SKVF-R models.)
WtrLeakDet:
Ok
* (Ok, Leak)
Displays whether a water leak has been detected.
If
Leak
is displayed, it indicates that there is a leak within the water
line.
RelayFuse:
Normal
* (Normal, Blown Fuse)
Displays the current status of the PCB fuse.
If
Blown Fuse
is displayed, the fuse must be replaced.
PowerFdbck:
Current value
* (min: 0%, max: 100%)
Displays the value of the power output feedback.
AlarmRelay:
Current value
* (Off, On)
Displays the status of the alarm warning relay.
ServiceRelay:
Current value
* (Off, On)
Displays the status of the service warning relay.
WaterSupplyValve:
Current value
* (Off, On)
Displays the status of the normally open water supply valve.
DrainValve:
Current value
* (Off, On)
Displays the status of the normally open drain valve.
(Only appears for SKVF-R models.)
Pump:
Current value
* (Off, On)
Displays the status of the circulation pump.
(Only appears for SKVF-R models.)
ECMFanSig:
Current value
* (min: 0V, max: 10V)
Displays the control signal value of the ECM fan.
System
SysStatus:
Operational
* (Operational, Operational Read-Only,
Download required, Download in progress,
Non-operational, Backup in progress)
Displays the current system status.
Vendor:
Neptronic
*
Displays the name of the vendor of the product. (Always Neptronic)