FG7B CONTROLLER: Hardware
JUMPER SETTINGS
Jumper setting as viewed with terminals at the bottom.
TTL Serial JP7 (2) To the left if serial TTL is selected (For Nemlink communication)
To the right if RS 485 or RS 232 communication is required
RS485/RS232 JP8 (2) To the left for RS 485 communication
To the right for RS 232 communication
RS485out JP3 (1) Down to enable RS 485 transmitting (standard)
Up to disable RS 485 transmitting (nonstandard use)
RS485in JP2 (1) Up to enable RS485 receiving (standard)
Down to disable RS485 receiving (nonstandard use)
Line Bias JP1 (2) Up to have line bias (star configurations)
Down for no line bias (daisy chain configuration)
Watch Dog timer 1 JP6 (1) Down for auto reset with transmission failure of the control unit
Up for no auto reset of the control unit
Watch Dog timer 2 JP4 (1)
Down for auto reset of the power supply with transmission
failure of the control unit
Up for no auto reset of the power supply
CONNECTORS
The connectors on the IOT1601JM board are self-explanatory. However, if communication will be
made through a NemLink card, then the connector J7 should be used with the comms cable
supplied with the unit (jumper selection TTL Serial). Also note that the FG7-Druid does not
support RS485 multidrop, only daisy chain – so there is a RS485 OUT and a RS485 IN terminal.
The TAUT Wire terminal is not used in the FG7-Druid controller.
PUSH BUTTONS
There are two push buttons on the green board. The one is marked “B3 PWR” (Power) and the
other “B3 RESET”. The B3 PWR button is used to manually power the control unit on and off, this
is usually required when programming the settings on the FG7-Druid. The B3 RESET button is
used to manually reset the FG7-Druid Controller.