30
7 RS485 Network K
h. Ensure the energizer is restored to factory default:
i. Reconnect the battery power. [2]
ii. Reconnect the mains power. [1]
iii. Within 60 seconds of reconnecting the power, enter 2389# on the keypad.
i. Enter installer mode by entering 012345*0# on the keypad. Ensure the
energizer LCD display turns purple. [8]
j. Configure the network address from by entering 51xx*#, where xx is the
address from 1 to 32. Energizer addresses must be chronologically configured
starting at 1. For example, three energizers on a network with addresses 5, 18
and 22 is not allowed, as they need to be addressed 1, 2 and 3. Relay boards
and energizers are addressed separately from 1 to 32.
k. Exit installer mode by entering *#. Ensure the energizer LCD display turns blue. [8]
l. Ensure the energizer network address is displayed on the LCD. [8]
m. Route the cables out the bottom of the energizer enclosure and install the lid.
4. For the RS485 8-way Relay Board:
a. Disconnect the power connector. [1]
b. Configure jumper JP1 for “NO” for data pass through. [2]
c. Configure jumper JP2 for daisy chain. [3]
4
5
2
3
6
1