MR-WM – WALL MOUNT INSTALLATION (Ordered Separately)
STEP 5:
Install Back Cover Plate with 4x M4 Flat head screws
and adhesive backed gasket. Apply gasket with
adhesive side applied to mount main body.
Torque to 2 N-m (17 in-lbs)
STEP 6:
Mount fixture assembly to desired location using
4x 1/4-20 OR M6 Screws or Bolts.
STEP 7:
Install appropriate Listed 3/4” NPT cable gland for cable
size to desired entry location and be sure to follow all
applicable local electrical codes for the specific hazardous
locations. Torque cable gland base and dome nut to
manufacturer's recommended specification. OR Install
Direct Rigid Conduit as per local electrical code. For direct
rigid conduit installation, torque hand tight plus 2 to 3
turns.
NOTE:
To aid in assembly and protection against ingress use
of a petrolatum or soap thickened mineral oil based
thread lubricant/sealant is necessary.
STEP 8:
Resume installation instructions provided with fixture.
(STEP 4)
145mm
145mm
4 x 7mm