RC/LRC/RX/LRX Series - New Construction Frame

Lumination

TM

 LED Luminaire

Installation Guide

BEFORE YOU BEGIN

Read these instructions completely and carefully.

 NOTICE

Lamp Housings RC6, RC8 or LRC6, LRC8 or RX6, RX8 or LRXR4, LRXR6, LRXR8 may be assembled with part FRAMExR. When Lamp Housings RC6,
RC8 or LRC6, LRC8 or RX6, RX8 or LRXR4, LRXR6, LRXR8 is assembled with Part FRAMExR the final assembly complies with UL 1598 category IFAO
recessed luminaire requirements. LRX products are suitable for wet location covered ceiling only.
Les boîtiers de lampes RC6, RC8 ou LRC6, LRC8 ou RX6, RX8 ou LRXR4, LRXR6, LRXR8 peuvent être montés avec la pièce FRAMExR. Lorsque les
boîtiers des lampes RC6, RC8 ou LRC6, LRC8 ou RX6, RX8 ou LRXR4, LRXR6, LRXR8 sont montés avec la pièce FRAMExR, le montage final respecte
les exigences des luminaires encastrés de la catégorie IFAO de la norme UL 1598. LRX produits conviennent pour emplacement humide couverte
au plafond uniquement.

Save These Instructions

Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.

Prepare Electrical Wiring

Electrical Requirements

The LED luminaire  must be connected to the mains 

supply according to its ratings on the product label.

Grounding Instructions

The grounding and bonding of the overall system 

shall be done in accordance to local electric code of 

the country where the luminaire is installed.

 WARNING/AVERTISSEMENT

RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.

  Minimum size 18 AWG or 14 AWG for continuous runs. 

RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des fils approuvés par UL pour les entrées/sorties de  

 

  connexion. Taille minimum 18 AWG ou 14 AWG pour les rangées continues.

Содержание Lumination RC Series

Страница 1: ...quement Save These Instructions Use only in the manner intended by the manufacturer If you have any questions contact the manufacturer Prepare Electrical Wiring Electrical Requirements The LED luminaire must be connected to the mains supply according to its ratings on the product label Grounding Instructions The grounding and bonding of the overall system shall be done in accordance to local elect...

Страница 2: ...on L brackets Mounting brackets 3 Slide hanger bars through adjustable mounting brackets 4 Option A Mount fixture by attaching hanger bars to T Grid ceiling BH3 SKU 94890 Option B Mount fixture with EMT conduit Note Supplied by 3rd party Bars Conduit A B Adjust height and tighten wing nut 5 Adjust fixture height to be flush with ceiling and tighten both mounting bracket wing nuts Components Provid...

Страница 3: ...C Wiring Diagram DRIVER TPC Black Red Lead White Lead Black Lead White Lead L N G PSU Enclosure Blue Lead 0 10V Purple Dimming Lead 0 10V Grey Dimming Lead Black Lead 120V ONLY Red Lead 277V ONLY NOTE Through Wiring for RC series 15A Circuit Lumen Level Maximum Number of Fixtures 120V Input 277V Input 1000 84 195 1500 77 179 2000 59 138 3000 38 89 4000 24 57 Minimum Spacing Requirements for all Fi...

Страница 4: ...hang freely Plug together the light fixture to the driver enclosure with the supplied quick connects and assemble the connector housing when finished Feed button stop and toggle through hole in bracket Safety tether Button stop Toggle Assembled connector housing Connect two quick connects Cut cable tie on light fixture Position fixture so L bracket does not interfere with springs Align the fixture...

Страница 5: ...e se trouve sur le chemin du ressort à sa libération 17 Load springs into upright position by twisting the springs upward and carefully insert the fixture to the hole of the frame Ensure fixture is secure Springs up 16 Connect the two quick connectors and reassemble the connector box Reassembled connector box Connect plugs Final installation position for springs Push fixture through the hole in th...

Страница 6: ... and gray dimming wires to the violet and gray wires of the fixture NOTE Please cover dimming leads with wire nuts if you won t connect with dimming leads Dimming compatibility for both 0 10V and phase cut please refer to GE website www gelighting com dimming AC line 18 0 10 Volt Dimming Gray 0 10V 0 10V Violet To 0 10V Dimmer LED Driver Wiring Diagram L Dimming N Dimming Ground LRX Fixture Black ...

Страница 7: ... chemin des ressorts de torsion car ils présentent un risque de pincement lorsqu ils sont libérés Les ressorts seront libérés au moment de fléchir le bras vers le bas Faites attention à ce qu aucune partie du corps ne se trouve sur le chemin du ressort à sa libération 19 20 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not...

Отзывы: