background image

3

6

Open RC or LRC PSU box cover, disconnect AC conduit. Remove AC conduit wire from PSU box knockout hole using

flat head screw driver.

Screwdriver tip

Remove cover

AC conduit

Remove 

AC wires

7

Insert AC line wires into the PSU box through

the knockout hole and connect wires (see wiring 

diagrams at right).

AC line (Line, Neutral and Ground)

RC Wiring Diagram

DRIVER

TPC

Black (+) Lead
White (-) Lead

Black (+) Lead

L    N   G

PSU Enclosure

*Blue/Red (+) Lead 

(0-10V) Purple (+) Dimming Lead

(0-10V) Grey (-) Dimming Lead

Blue Lead - 120V ONLY

Red Lead - 277V ONLY

*NOTE:

LRC Wiring Diagram

DRIVER

TPC

Black /Red (+) Lead
White (-) Lead

Black (+) Lead

White (-) Lead

L    N   G

PSU Enclosure

Blue (+) Lead 

(0-10V) Purple (+) Dimming Lead

(0-10V) Grey (-) Dimming Lead

Black Lead - 120V ONLY

Red Lead - 277V ONLY

*NOTE:

Through Wiring for RC-series 15A Circuit

Lumen Level

Maximum Number of Fixtures

(120V Input / 277V Input)

1000

84 / 195

1500

77 / 179

2000

59 / 138

3000

38 / 89

4000

24 / 57

Minimum Spacing Requirements 

for all Fixture Configurations

Center to center of adjacent luminaires

24”

Top of Luminaire to overhead building member

3”

Luminaire center to side building member

12”

(For any other information refer to RC-series or LRC-series Installation Guides)

RC/LRC-Series Mounting

(RX-Series Mounting skip to step 15. LRXR-Series Mounting skip to step 18)

Содержание Lumination RC Series

Страница 1: ...quement Save These Instructions Use only in the manner intended by the manufacturer If you have any questions contact the manufacturer Prepare Electrical Wiring Electrical Requirements The LED luminaire must be connected to the mains supply according to its ratings on the product label Grounding Instructions The grounding and bonding of the overall system shall be done in accordance to local elect...

Страница 2: ...on L brackets Mounting brackets 3 Slide hanger bars through adjustable mounting brackets 4 Option A Mount fixture by attaching hanger bars to T Grid ceiling BH3 SKU 94890 Option B Mount fixture with EMT conduit Note Supplied by 3rd party Bars Conduit A B Adjust height and tighten wing nut 5 Adjust fixture height to be flush with ceiling and tighten both mounting bracket wing nuts Components Provid...

Страница 3: ...C Wiring Diagram DRIVER TPC Black Red Lead White Lead Black Lead White Lead L N G PSU Enclosure Blue Lead 0 10V Purple Dimming Lead 0 10V Grey Dimming Lead Black Lead 120V ONLY Red Lead 277V ONLY NOTE Through Wiring for RC series 15A Circuit Lumen Level Maximum Number of Fixtures 120V Input 277V Input 1000 84 195 1500 77 179 2000 59 138 3000 38 89 4000 24 57 Minimum Spacing Requirements for all Fi...

Страница 4: ...hang freely Plug together the light fixture to the driver enclosure with the supplied quick connects and assemble the connector housing when finished Feed button stop and toggle through hole in bracket Safety tether Button stop Toggle Assembled connector housing Connect two quick connects Cut cable tie on light fixture Position fixture so L bracket does not interfere with springs Align the fixture...

Страница 5: ...e se trouve sur le chemin du ressort à sa libération 17 Load springs into upright position by twisting the springs upward and carefully insert the fixture to the hole of the frame Ensure fixture is secure Springs up 16 Connect the two quick connectors and reassemble the connector box Reassembled connector box Connect plugs Final installation position for springs Push fixture through the hole in th...

Страница 6: ... and gray dimming wires to the violet and gray wires of the fixture NOTE Please cover dimming leads with wire nuts if you won t connect with dimming leads Dimming compatibility for both 0 10V and phase cut please refer to GE website www gelighting com dimming AC line 18 0 10 Volt Dimming Gray 0 10V 0 10V Violet To 0 10V Dimmer LED Driver Wiring Diagram L Dimming N Dimming Ground LRX Fixture Black ...

Страница 7: ... chemin des ressorts de torsion car ils présentent un risque de pincement lorsqu ils sont libérés Les ressorts seront libérés au moment de fléchir le bras vers le bas Faites attention à ce qu aucune partie du corps ne se trouve sur le chemin du ressort à sa libération 19 20 This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not...

Отзывы: