4 NCB Service Manual
Version 1.0
Requirements for the State of Massachusetts
This appliance must be installed by a licensed plumber or gas fitter in accordance with the Massachusetts Plumbing and Fuel Gas Code
248 CMR Sections 2.00 and 5.00.
IMPORTANT: In the State of Massachusetts (248 CMR 4.00 & 5.00)
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is
less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following
requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery
back‐up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall
observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the
dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the
property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide
detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back‐up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance
or equipment. The sign shall read, in print size no less than one‐half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF
ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with
the provisions of 248 CMR 5.08(2)(a)1 through 4.
Содержание NCB-180
Страница 3: ......
Страница 4: ...Revisions Version Description of changes Date 1 00 First Issue October 27 2013 1 00 Reviewed BY...
Страница 16: ......
Страница 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Страница 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Страница 142: ...Memo...
Страница 143: ...140 NCB Service Manual Version 1 0 Memo...
Страница 144: ...Memo...
Страница 145: ...142 NCB Service Manual Version 1 0 Memo...
Страница 146: ...Memo...
Страница 147: ...144 NCB Service Manual Version 1 0 Memo...
Страница 148: ...Memo...
Страница 149: ...146 NCB Service Manual Version 1 0 Memo...