14.
Place the PCB assembly back on to the boiler and tighten
the three screws.
15.
Check the labels carefully and then connect all the wires.
16.
For LP, set DIP SW2 #2 to On. For NG, set DIP SW2 #3 to Off.
WARNING
Ensure that you have turned off the power to the boiler
before accessing the DIP switches.
DANGER
When conversion is required, be sure to set the Front
Panel DIP switches according to the supply gas type.
Failure to properly set the DIP switches could cause
carbon monoxide poisoning, resulting in severe
personal injury or death.
17.
Turn on the gas and water supply to the boiler.
18.
Measure and adjust the gas/air ratio.
Option 1. Using Combustion Analyzer (recommended)
a.
Loosen the screw, rotate the plate and remove the
gasket to access the emissions monitoring port as
shown in Figure 7.
b.
Insert the analyzer into the port (Figure 7).
Figure 7
Boiler
Fuel
High fire
Low fire
%CO
2
%CO
2
NCB-180
NG
8.9
9.5
LP
10.2
10.8
NCB-210
NG
8.9
9.5
LP
10.2
10.8
NCB-240
NG
8.9
9.5
LP
10.2
10.8
Table 2. CO
2
and CO value
(CO
2
values must be within 0.5% of the values listed.)
Содержание NCB-180
Страница 3: ......
Страница 4: ...Revisions Version Description of changes Date 1 00 First Issue October 27 2013 1 00 Reviewed BY...
Страница 16: ......
Страница 135: ...132 NCB Service Manual Version 1 0 7 2 Burner Assembly...
Страница 139: ...136 NCB Service Manual Version 1 0 7 4 Fan Gas Assembly...
Страница 142: ...Memo...
Страница 143: ...140 NCB Service Manual Version 1 0 Memo...
Страница 144: ...Memo...
Страница 145: ...142 NCB Service Manual Version 1 0 Memo...
Страница 146: ...Memo...
Страница 147: ...144 NCB Service Manual Version 1 0 Memo...
Страница 148: ...Memo...
Страница 149: ...146 NCB Service Manual Version 1 0 Memo...