It is recommended that the unit be secured into its position in order to avoid any displacement. Do not use makeshift
compromises during installation.
Floor Protection
This unit must be installed with floor protection of a non-combustible protective floor pad of a
minimum 3/8” (10mm)
thickness material or a masonry hearth. Follow the next diagram for sizing.
Minimum Installation Clearance to Combustibles
Minimum clearances to combustible surfaces must be maintained. See diagrams below and on pages 11-16. Keep all
combustibles outside of these clearance areas. INSTALL VENTING AT CLEARANCES SPECIFIED BY THE VENT
MANUFACTURER. Clearances may only be reduced by means approved by the regulatory authority.
Alcove Clearances
Maximum Alcove depth: 36”. Minimum Alcove height: 57.5” Minimum Alcove Width: 41”
Vent Termination Locations