Chapter 2
Configuration and Installation
© National Instruments Corporation
2-13
SCXI-1160 User Manual
When connecting your signals to the SCXI-1324 for use with the SCXI-1160, follow the labeling
as indicated in Figure 2-6, SCXI-1324 Parts Locator Diagram.
Signal Connection. To connect the signal to the terminal block, use the following procedure:
1. Remove the grounding screw of the top cover.
2. Snap out the top cover of the shield by placing a screwdriver in the groove at the bottom of
the terminal block.
3. Slide the signal wires, one at a time, through the front panel strain relief. Additional
insulation or padding may be added if necessary.
4. Connect the wires to the screw terminals.
5. Tighten the strain relief by tightening the larger screws.
6. Snap the top cover back in place.
7. Replace the grounding screw to ensure proper shielding.
8. Install contact protection as previously described if your load is inductive.
9. Connect the terminal block to the SCXI-1160 front connector as explained in the SCXI-1324
Installation section, the next section in this chapter.
Figure 2-6 shows a parts locator diagram for the SCXI-1324 terminal block.