Chapter 2
Installing and Configuring Hardware and Software
©
National Instruments Corporation
2-17
1.
Plug the Combicon-style connector into the CAN port.
Figure 2-16.
CAN Port Terminals on the FP-1300
2.
Connect a twisted-pair cable to the CAN_H and CAN_L terminals.
The maximum recommended cable length between the FP-1300 and
the CAN network is 0.3 m (12 in.). CAN_H and CAN_L carry the data
on the CAN network.
3.
Connect a 10–30 VDC power supply to the V+ and V– terminals.
V+ and V– supply bus power to the CAN bus on the FP-1300.
4.
If you are using shielded cable, connect one end of the shield to the
Shield terminal. This connection is not required for all CAN networks.
Connecting a cable shield to the Shield terminal helps reduce noise.
5.
Connect the other end of the CAN cable to a connector on the CAN
network.