© National Instruments
|
5-1
5
Analog Output
Many X Series devices have analog output functionality. X Series devices that support analog
output have either two or four AO channels that are controlled by a single clock and are capable
of waveform generation. Refer to Appendix A,
, for information
about the capabilities of your device.
Figure 5-1 shows the analog output circuitry of X Series devices.
Figure 5-1.
X Series Analog Output Circuitry
The main blocks featured in the X Series analog output circuitry are as follows:
•
DACs
—Digital-to-analog converters (DACs) convert digital codes to analog voltages.
•
AO FIFO
—The AO FIFO enables analog output waveform generation. It is a
first-in-first-out (FIFO) memory buffer between the computer and the DACs. It allows you
to download the points of a waveform to your X Series device without host computer
interaction.
•
AO Sample Clock
—The AO Sample Clock signal reads a sample from the DAC FIFO and
generates the AO voltage.
•
AO Reference Selection
—The AO reference selection signal allows you to change the
range of the analog outputs.
AO 2
AO
3
DAC2
DAC
3
AO D
a
t
a
AO FIFO
AO
Sa
mple Clock
AO Reference
S
elect
AO 0
AO 1
DAC0
DAC1
Содержание 6368
Страница 1: ...PXIe 6368...