background image

6

Installation Guide

 | Comfort Pack with 80% Gas Heat

Safety Warnings!

IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE 

FURNACE MUST BE REPLACED, IT MUST BE REPLACED 

WITH WIRING MATERIAL HAVING A TEMPERATURE 

RATING OF AT LEAST 90°C.
THIS FURNACE MUST BE INSTALLED SO THERE ARE 

PROVISIONS FOR VENTILATING AIR.
SHOULD OVERHEATING OCCUR, OR THE GAS SUPPLY 

FAIL TO SHUT OFF, SHUT OFF THE MANUAL GAS 

VALVE TO THE FURNACE BEFORE SHUTTING OFF THE 

ELECTRICAL SUPPLY.

THESE UNITS ARE NOT APPROVED FOR MOBILE 

HOME APPLICATIONS. SUCH USE COULD RESULT IN 

PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH.

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO 

QUALIFIED, LICENSED SERVICE PERSONNEL FOR 

PROPER INSTALLATION, ADJUSTMENT AND OPERATION 

OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY 

BEFORE ATTEMPTING INSTALLATION OR OPERATION. 

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY 

RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, 

SERVICE OR MAINTENANCE POSSIBLY RESULTING 

IN FIRE, ELECTRICAL SHOCK, PROPERTY DAMAGE, 

PERSONAL INJURY OR DEATH.

DO NOT USE OXYGEN TO PURGE LINES OR PRESSURIZE 

SYSTEM FOR LEAK TEST. OXYGEN REACTS VIOLENTLY 

WITH OIL, WHICH CAN CAUSE AN EXPLOSION 

RESULTING IN SEVERE PERSONAL INJURY OR DEATH.

GAS-FIRED APPLIANCES ARE NOT DESIGNED FOR 

USE IN HAZARDOUS ATMOSPHERES CONTAINING 

FLAMMABLE VAPORS OR COMBUSTIBLE DUST, 

IN ATMOSPHERES CONTAINING CHLORINATED 

OR HALOGENATED HYDROCARBONS, OR IN 

APPLICATIONS WITH AIRBORNE SILICONE 

 

SUBSTANCES. SEE HAZARD LEVELS BELOW. 

!

WARNING

!

WARNING

!

WARNING

!

WARNING

!

CAUTION

Before You Start

This unit is shipped with a cooling chassis installed in the 

cabinet. Prior to installing the unit in the wall opening, the 

shipping bolts located at the bottom on both sides of the cabinet 

must be removed to allow for removal of the cooling chassis. 

1/4" hole plugs provided with the unit should be installed in the 

holes to prevent air leakage. Shipping bolts are located on both 

sides below this sticker:

THE SHIPPING BOLTS MUST BE REMOVED PRIOR 

TO INSTALLATION OF THE CABINET TO PERMIT  

REMOVAL OF THE CHASSIS. INSTALL THE HOLE 

PLUGS PROVIDED.

14299588

This unit is designed and approved for through-the-wall 

installation only. The unit must be installed a minimum of 8” 

above finish floor. If this unit is installed in a residential 

garage, it must be installed so that the ignition source and 

burners are located not less than 18 inches (457 mm) above 

the floor, and it must be located or protected to avoid physical 

damage by vehicles. The entire unit must not be installed 

outside.

 The grille side of the unit should extend 3/4" beyond the 

exterior wall to allow moisture that may enter the outdoor 

section to drain. The pitch of the internal drain pans toward the 

outside will assure proper drainage when the cabinet is installed 

level. 

Masonry walls must have a lintel to support the wall.

The interior of the unit may be installed with zero clearances to 

adjacent combustible surfaces. 

The unit shall not be installed 

directly on carpeting, tile or other combustible material, 

except wood flooring. 

In order to be able to remove the chassis, 

29" of open area must be left unobstructed in front of the access 

panels. The 3/4" O.D. drain pan connection should be connected 

to the building drain using the flexible tubing included and 

a trap. The secondary drain offers protection from overflow.  

The secondary drain feature is piped into the base of the unit 

and drains through the weep holes outside. Reconnect 3” piece 

of clear flexible tubing to secondary drain on drain pan. Position 

secondary drain through grommet of chassis and connect to 

flexible tubing (prime trap prior to operating).

The grille side must be kept free of any obstructions that 

will reduce or alter the air flow pattern. 

The unit must be 

installed at least 4 feet (1.22 m) from electric meters, gas 

meters, regulators, and relief equipment. The vent of the 

unit is located at the front grille. Distances from adjacent 

public walkways, adjacent buildings, openable windows, and 

building openings must be consistent with the National Fuel 

Gas Code ANSI Z223.1 and/or CAN/CGA-B149 installation 

codes, as well as local codes.

If an optional architectural grille is to be used on standard 

units, the stamped grille provided 

must 

be removed. Consult 

the factory prior to ordering product(s) that require an optional 

architectural grille.

Содержание Comfort Pack U Series

Страница 1: ...ith the homeowner for future reference 80 AFUE National Comfort Products A Division of National Refrigeration and Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 5908 800 523 7138...

Страница 2: ......

Страница 3: ...Functions page 17 High Altitude Operation page 17 18 Gas Piping Venting Pressures page 19 20 Ignition System page 21 Start up page 22 23 Special Notes for Extremely Cold Weather Areas page 23 24 Gas...

Страница 4: ...80 Gas 9 95 Gas E Electric 4 Refrigerant 4 R410A 18 Clg Capacity 12 1Ton 18 1 5Ton 24 2Ton 38 Htg Capacity 25 25 MBH 28 28 MBH 32 32 MBH 38 38 MBH 43 43 MBH 50 50 MBH 51 51 MBH 64 64 MBH 00 0 kW U Se...

Страница 5: ...IFIED BY NATIONAL CODES ATTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE PERSONAL INJURY OR DEATH WARNING WARNING WARNING DO NOT USE THIS APPLIANCE IF ANY...

Страница 6: ...299588 This unit is designed and approved for through the wall installation only The unit must be installed a minimum of 8 above finish floor If this unit is installed in a residential garage it must...

Страница 7: ...ments Be sure that the electrical data specified on the unit rating plate corresponds to what is available at the installation site and NEC for installation requirements This unit MUST be installed in...

Страница 8: ...an handle the load imposed by the unit IMPORTANT This Document is customer property and is to remain with this unit Please refer to service information pack upon completion of work to register the uni...

Страница 9: ...cal damage by vehicles Secondary Drain Trap Install Instructions 1 The trap and 2 piece of clear flexible 1 2 ID tubing are shipped loose to prevent damage They should be installed after the Comfort P...

Страница 10: ...of these decorative grilles The less resistive these grilles are to air flow the better the units performance will be Outdoor louvers provided by others must be approved by NCP to maintain unit perfo...

Страница 11: ...snow level 12 in B Clearance to a window or door that may be opened 9 in for appliances 10 000 Btuh 3 kW and 50 000 Btuh 15 kW 12 in for appliances 50 000 Btuh 15 kW C Clearance to a permanently clos...

Страница 12: ...grounding must be made in accordance with the National Electric Code ANSI NFPA No 70 latest edition or in Canada the Canadian Electrical Code Part I C S A Standard C22 1 In addition the installer sho...

Страница 13: ...respond to that specified on the unit rating plate and that the service provided by the utility is sufficient to handle the additional load imposed by this equipment Power wiring must comply with nati...

Страница 14: ...tivated manually reset switch The flame rollout switch is located centrally on the top of the burner assembly It is factory set and is non ad justable If the setpoint is reached the flame rollout acts...

Страница 15: ...rt Pack Dimension Drawing 5 Side view 3 51 64 1 1 4 31 17 32 16 7 43 64 43 15 25 32 26 57 64 1 1 32 31 15 32 7 15 16 28 7 21 32 4 23 64 1 3 4 RETURN JUNCTION BOX GAS CONNECTION LOW VOLTAGE THERMOSTAT...

Страница 16: ...he pressure switch is open the control proceeds to 2 Pre purge 2 Pre purge The control energizes the venter motor and waits for the pressure switch to close If the pressure switch does not close withi...

Страница 17: ...gnition the control de energizes the gas valve energizes the blower motor on heat speed and venter motor remains energized The blower motor is shut off after a short period When the blower motor de en...

Страница 18: ...ment label in the plastic bag that contained these instructions Using a permanent marker fill in the pressure setting Adhere the label on the heater near the gas valve so that it is conspicuous to som...

Страница 19: ...manual valve on the heater All piping must be in accordance with requirements outlined in the National Fuel Gas Code ANSI Z223 1a latest edition or CAN CGA B149 1 and B149 2 Gas supply piping install...

Страница 20: ...ed to 3 5 w c Inlet supply pressure to the valve for natural gas must be a minimum of 5 w c and a maximum of 14 w c Normally field adjustment should not be required For Propane Gas When the heater lea...

Страница 21: ...thermostat has been satisfied the system de energizes the gas valve the venter motor goes through a 30 second post purge and the fan motor remains energized for an additional time NOTE This is a three...

Страница 22: ...es of trapped air 5 Check electrical wiring Be sure all wire gauges are as recommended A service disconnect switch should be used Verify that fusing or circuit breakers are adequate for the load use 6...

Страница 23: ...follow the steps in the WARNINGS above or on the Operating Label on the heater If you do not smell gas proceed to the next step 6 Turn the gas control knob counterclockwise to ON Close the access doo...

Страница 24: ...oling chassis must be maintained regularly to assure that the unit provides optimal performance and energy efficiency The intervals between replacing depends entirely on the cleanliness of the return...

Страница 25: ...cover must be reinstalled IF YOU TURN OFF POWER SUPPLY TURN OFF THE GAS SEE HAZARD LEVELS PAGE 5 THE MATERIAL CONTAINED IN THE MAINTENANCE AND SERVICE SECTION OF THIS MANUAL IS DESIGNED TO AID A QUALI...

Страница 26: ...ach end Loosen burner assembly by removing only the two screws indicated Burner Assembly Secondary Air Shield End Cap Remove secondary air shield end cap by removing four screws indicated Remove screw...

Страница 27: ...e fuse Do not attempt to disassemble the control module However each heating season check the lead wires for insulation deterioration and good connections Proper operation of the direct spark ignition...

Страница 28: ...spect the burner control compartment for signs of excessive heat and burned wiring If the compartment appears normal reset by depressing the red button on the switch 15 to 20 minutes are required for...

Страница 29: ...ctions to Slide Out the Furnace After removing front panels 1 Remove the 4 screws indicated at the right Gas Line Power Cord 2 Remove the patch plate Gas Line Power Cord Front Furnace Baffle 3 Remove...

Страница 30: ...insulation when pulling the heat exchanger furnace assembly forward 4 Unplug 2 molex plugs before sliding out the heat exchanger furnace assembly Lift Pull Forward Power Cord 6 With your right hand r...

Страница 31: ...0 15 CP841838UA 208 230 60 1 6 5 37 5 1 4 1 83 3 6 1 3 3 0 11 3 13 0 15 CP841851UA 208 230 60 1 6 5 37 5 1 4 1 83 3 6 1 3 3 0 11 3 13 0 15 CP841864UA 208 230 60 1 6 5 37 5 1 4 1 83 3 6 1 3 3 0 11 3 1...

Страница 32: ...e should be as follows 28MBTU 52 5 F Nominal 45 F to 60 F 38MBTU 52 5 F Nominal 45 F to 60 F 51MBTU 55 F Nominal 45 F to 65 F 64MBTU 67 F Nominal 60 F to 80 F In order to calculate CFM use the formula...

Страница 33: ...590 35 0 565 36 5 540 38 2 525 39 3 510 40 5 Orange 5 440 46 9 425 48 6 410 50 4 400 51 6 390 52 9 Comfort Pack Gas CFM and Temperature Rise 38 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3...

Страница 34: ...7 565 66 6 540 69 6 525 71 6 510 73 7 Orange 5 440 85 5 425 88 5 410 91 7 400 94 0 390 96 4 Comfort Pack Gas CFM and Temperature Rise 64 000 BTU Input UNIT SIZE COLOR SPEED 1 w c TD 2 w c TD 3 w c TD...

Страница 35: ...00 Blue 3 560 535 520 510 500 Black 4 440 425 410 390 370 Orange 5 390 360 330 310 290 CP8418 UA Red 1 760 745 730 715 700 Yellow 2 650 640 630 615 600 Blue 3 560 535 520 510 500 Black 4 440 425 410 3...

Страница 36: ...BLACK WHITE BLACK C F H CAP CFM C S R COMP EBM 208 230 C XFMER CC LPS TRANSFORMER FACTORY SET POINT IS 230V FIELD ADJUSTMENT REQUIRED FOR 208V APPLICATION 1 2 3 4 5 SPEED TERMINAL 1 HIGH 2 MED HIGH 3...

Страница 37: ...1 Set thermostat at lowest setting 2 Turn on manual gas valve 3 Turn on power to unit 4 Set thermostat at desired setting 5 Thermostat calls for heat energizing the venter motor 6 Venter pressure swi...

Страница 38: ...rol at the thermostat or 5 main power Replace combustion air proving switch 6 7 a If 24 volt is measured at the valve connections and valve remains closes replace valve b Check and tighten all wiring...

Страница 39: ...Bottom Panel 14256600 LP Gas Orifice N A 14208339 14208340 14208341 Rail 14256605 Flame Rollout Switch 14208314 Horizontal Air Divider 14256670 Orifice Adapter 14208315 Vertical Air Divider 14256671 O...

Страница 40: ...4275146 14275117 14275118 Outdoor Fan Motor 14270057 14270044 14270057 Outdoor Coil Mount 14256430 14256434 Drier 14275947 Outdoor Fan 14214042 Outdoor Motor Mount 14270101 Indoor Blower Motor 1427006...

Страница 41: ...ding between Terminals C R __________ 5 Compressor Winding OHM Reading between Terminals R S __________ 6 Compressor Winding OHM Reading between Terminals C Ground __________ 7 Compressor Winding OHM...

Страница 42: ...to the goods and are in lieu of and exclude all other warranties express or implied arising by operation of law or otherwise including without limitation merchantability and fitness for a particular p...

Страница 43: ...shall render the warranty void B Compressors In addition to the above referenced requirements Customer is also required to purchase a replacement compressor and return the original compressor to Natio...

Страница 44: ...20 20 HEATING A C EQUIPMENT NATIONAL COMFORT PRODUCTS National Comfort Products A Division of National Refrigeration Air Conditioning Products Inc 539 Dunksferry Road Bensalem PA 19020 1 800 523 7138...

Отзывы: