Installation Guide
| Comfort Pack with 80% Gas Heat
DSI INTEGRATED CONTROL MODULE
CONTROL
STATUS
GREEN LED
STEADY ON
FAST FLASH
1 FLASH
2 FLASH
3 FLASH
4 FLASH
STEADY OFF
Normal operation, no call for heat
Normal operation, call for heat
In lockout from failed ignition or flame loss
Pressure switch does not close for 240 seconds
Limit switch or rollout switch open
Pressure switch is closed before venter is energized
Internal control fault or no power
FLAME
STATUS
YELLOW LED
STEADY ON
SLOW FLASH
FAST FLASH
Flame sensed
Weak flame (current below 1.0 microamps = +/-50%)
Undesired flame (valve open and no call for heat)
FAN OFF DELAY
TIME
SWITCH
1
2
90
OFF
ON
120
OFF
OFF
160
ON
OFF
45
ON
ON
TEST
Y
FLAME
LED
G
OK
LED
FIELD CONTROL WIRING
TOTAL WIRE
LENGTH
DISTANCE
FROM UNIT
TO CONTROL
MIN. RECOMMENDED
WIRE GAUGE
150’
250’
350’
75’
125’
175’
#18 GAUGE WIRE
#16 GAUGE WIRE
#14 GAUGE WIRE
Operation Sequence
1. Set thermostat at lowest setting.
2. Turn on manual gas valve.
3. Turn on power to unit.
4. Set thermostat at desired setting.
5. Thermostat calls for heat, energizing the venter motor.
6. Venter pressure switch closes, firing unit.
7. Burner flame is sensed, and in 20 seconds the fan motor is energized.
8. If the flame is extinguished during main burner operation, the integrated control system closes the main valve and must be reset by
interrupting power to the control circuit (see lighting instructions).
Notes
1. The following control is a field-installed option: thermostat.
2. Dotted wiring installed by others.
3. Caution: if any of the original wiring as supplied with the appliance must be replaced, it must be replaced with wiring material having a
temperature rating of at least 105°C except for sensor lead wire and limit wiring which must be 150°C.
4. Use 18 gauge wire for all low voltage wiring on the unit or follow chart above.
5. Line and fan motor branch wire sizes should be of a size to prevent voltage drops beyond 5% of supply line voltage.
(Use copper conductors only).
6. Ground wire must be used.