Installation Guide
| Comfort Pack with 80% Gas Heat
to route return ductwork to the unit or allow for unrestricted
airflow in an open return configuration. To reduce the possible
transmission of sound and vibration, a resilient material such as
rubber or cork should be installed between the support and the
base of the unit. All spaces around the top, sides, and bottom of
the exterior grille area should be caulked and sealed to the wall,
making sure that the openings for drainage in the bottom edge
are not blocked.
If the optional wall sleeve is used, caulk the spaces between the
sleeve and the wall. Completely fill the clearance on all sides
between the unit and the wall sleeve with a polyurethane foam
sealant (follow manufacturer’s suggested application manual).
NOTE: FOR EASE OF INSTALLATION, INSTALL
THE CABINET INTO THE WALL SLEEVE FIRST
WITHOUT THE COOLING CHASSIS. THEN SLIDE
COOLING CHASSIS IN AFTER CABINET IS IN
PLACE.
Drainage
The 3/4" I.D. flexible tubing included should be connected to the
Comfort Pack primary drain connection so that it can easily be
disconnected if the cooling chassis must be removed. A trap
at least 2" deep should be provided close to the drain pan. The
tubing should not be higher than the bottom of the unit drain
pan at any point to assure proper drainage and allow chassis
removal. The drain line should pitch downward at least 1" per
10 ft. to an open building drain trap.
SECONDARY DRAIN TRAP
MUST BE INSTALLED
Drain Pan
3/4” I.D. Flexible Tubing Included
2”
min.
Pitch Downward 1” per 10ft.
Shaded Area Represents Components
Provided and Installed By Others
Highest Point Must Not Be Above
Bottom of Drain Pan
3/4” O.D. Drain Connection
(Primary Drain)
Be sure that the electrical service provided to the building can
handle the load imposed by the unit.
IMPORTANT — This Document is customer property and is to
remain with this unit. Please refer to service information pack
upon completion of work to register the unit’s warranty. These
instructions do not cover all variations in systems or provide
for every possible contingency to be met in connection with the
installation. Should further information be desired or should
particular problems arise which are not covered sufficiently
for the purchaser’s purposes, the matter should be referred to
your installing dealer or local distributor before contacting the
manufacture.
NOTE: THE UNIT MUST NEVER BE PLACED
ON ITS SIDE OR UPSIDE DOWN AS THE
COMPRESSOR OIL WILL RUN IN THE COOLING
CIRCUIT AND SERIOUSLY DAMAGE THE UNIT.
Installation
NOTE: INSTALLATION AND MAINTENANCE
INSTRUCTIONS SHOULD BE LEFT WITH THE
UNIT FOR FUTURE REFERENCE.
This unit must be installed in accordance with all applicable
codes. This unit is not to be used for temporary heating of
buildings or structures under construction.
FOR MAXIMUM PERFORMANCE, IT IS IMPERATIVE THAT
THE COOLING CHASSIS AIR DIVIDER BE SEALED TO THE
CABINET AIR SEAL. ANY LEAKAGE WILL ALLOW OUTSIDE
UNCONDITIONED AIR TO INFILTRATE AND MIX WITH THE
CONDITIONED AIR. THIS CONDITION WILL DEGRADE UNIT
PERFORMANCE. ALL UNITS SHOULD BE INSPECTED FOR
THIS CONDITION, AS DURING TRANSPORTATION AND
INSTALLATION THE SEALS CAN BE DISTURBED. IF REQUIRED,
A LIGHT BEAD OF CAULKING IS RECOMMENDED TO SEAL THE
CHASSIS, TO THE AIR SEAL TO ELIMINATE LEAKAGE.
OUTSIDE/UNCONDITIONED AIR MUST NOT BE INTRODUCED
INTO THE RETURN AIR STREAM OF THIS UNIT. THIS
CONDITION WILL ALSO DEGRADE THE PERFORMANCE
OF THE UNIT AND MAY VOID EQUIPMENT WARRANTY.
The unit must be installed through an exterior wall with the
back end extending 3/4” past the outside wall surface. Provide
support inside the building for the unit near the return air
opening. There should be enough clearance around the supports