5.1 MINIMUM CLEARANCE TO COMBUSTIBLES
* HORIZONTAL VENT SECTIONS
- A minimum clearance of 1" at the bottom and sides and 2" at the top of the
vent pipe in all horizontal runs to combustibles is required except for clearances in appliance enclosures, see
"MINIMUM ENCLOSURE CLEARANCES" section. Use
fi
restop spacer W010-1777 (supplied).
* VERTICAL VENT SECTIONS
- A minimum of 1" all around the vent pipe on all vertical runs to combustibles is
required. Use
fi
restop spacer W500-0096 (not supplied).
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible Framing:
-
0" to stand-offs
-
1" to bottom and sides of the vent pipe*
-
2" to top of the vent pipe*
Combustible Finishing:
-
0" to rear
-
0" to front face top and sides
-
13" recessed depth
Rear Vent:
-
39 1/8" to enclosure top from base of the unit
-
45 1/8" to ceiling from base of the unit
Top Vent:
-
53 1/8" to enclosure top from base of the unit
-
53 1/8" to ceiling from base of the unit
DO NOT BUILD INTO THIS AREA - IT MUST BE LEFT CLEAR TO PROVIDE ADEQUATE CLEARANCE
FOR THE VENT. IN THIS 14” WIDE AREA CENTRED ALONG THE FRONT OF THE APPLIANCE, NO
COMBUSTIBLES ARE ALLOWED.
!
WARNING
13
1
/
4
”
14”
MINIMUM
1
1
/
2
”
MAXIMUM
*KEEP FACING MATERIAL 1/4” FROM SIDE OF UNIT
TO ACHIEVE OPENING WIDTH OF 20
1
/
4
”.
NOTE: MUST BE MAINTAINED FOR THE FACING KIT
TO COVER THE OPENING.
* 1
/
4
”
1
1
/
2
”
MAXIMUM
*FINISHING
MATERIAL
OPENING
HEIGHT
MUST BE
34
1
/
8
”
CEMENT BOARD -
REQUIRED FOR
CONTEMPORARY
FRONT ONLY
(CFS19/CFK19)
NON-COMBUSTIBLE
MATERIAL