16
W415-1004 / B / 08.10.12
3.9 REAR EXIT HORIZONTAL TERMINATION
For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 35 feet
Example:
V
1
= 9 FT
V
2
= 6 FT
V
T
=
V
1
+ V
2
= 9 + 6 = 15 FT
H
1
= 3 FT
H
2
= 2 FT
H
3
= 1.5 FT
H
R
=
H
1
+ H
2
+ H
3
= 3 + 2 + 1.5 = 6.5 FT
H
O
= .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT
H
T
=
H
R
+ H
O
= 6.5 + 8.1 = 14.6 FT
H
T
+ V
T
= 14.6 + 15 = 29.6 FT
Formula 1:
H
T
< V
T
14.6 < 15
Formula 2:
H
T
+ V
T
< 35 FT
29.6 < 35
Since both formulas are met, this vent configuration is acceptable.
0
2.5
5
7.5
10
12.5
15
40
10
20
30
17.5
20
1.6
32.3
90°
V
1
V
2
H
1
H
2
90°
90°
90°
H
3
Simple venting configuration
(only two 90° elbows)
See graph to determine the required vertical rise
V
T
for the required
horizontal run
H
T
.
REQUIRED
VERTICAL
RISE IN
FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
H
T
The shaded area within the lines represents acceptable values for
H
T
and
V
T
(H
T
) < (V
T
)
16.6_2A
Содержание Vittoria GD19N
Страница 53: ...53 W415 1004 B 08 10 12 16 0 SERVICE HISTORY 43 1 ...
Страница 54: ...54 W415 1004 B 08 10 12 17 0 NOTES 44 1 ...
Страница 55: ...55 W415 1004 B 08 10 12 44 1 ...
Страница 56: ...56 W415 1004 B 08 10 12 ...
Страница 57: ...56 W415 1004 B 08 10 12 ...