31
W415-1004 / B / 08.10.12
4.6 GAS
INSTALLATION
30.1A
Installation and servicing to be done by a quali
fi
ed installer.
A.
Move the appliance into position and secure.
B.
If equipped with a
fl
ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.
C.
Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.
D.
When
fl
exing any gas line, support the gas valve so that the lines are not bent or kinked.
E.
The gas line
fl
ex-connector should be installed to provide suf
fi
cient movement for shifting the burner
assembly on it’s side to aid with servicing components.
F.
Check for gas leaks by brushing on a soap and water solution.
Do not use open fl ame.
!
WARNING
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS
SPARKS OR OPEN FLAMES.
SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT
WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE
PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT
THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND
ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.
ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG.
VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.
4.7 OPTIONAL WALL SWITCH
The main burner and Night Light
TM
switch is located behind lower access panel. For ease of accessibility, op-
tional remote wall switches may be installed in a convenient location for both burner and light operation.
The recommended maximum lead length depends on wire size:
WIRE SIZE
MAX. LENGTH
14
gauge
100
feet
16 gauge
60 feet
18 gauge
40 feet
Route 2-strand (solid core) wire through the electrical
hole located at the bottom left side of the unit. Connect
the wires from the main burner wall switch to the two
corresponding spade connectors on the back of the on/off switch for the burner located behind the lower ac-
cess panel. Repeat connecting the wires to the Night Light
TM
on/off switch for remote operation.
50.4
PILO
T
R502
T
2
0
0
2
0
0
2
!
WARNING
DO NOT CONNECT EITHER THE WALL SWITCH, THERMOSTAT OR GAS VALVE DIRECTLY TO 110
VOLT ELECTRICITY.