27
rough framing - before appliance installation
4.1.1 minimum clearance to combustible enclosures
single-sided
Shaded components (fi nish framing) must
be non-combustible materials.
note:
L
3” [76mm] top (outside
of enclosure)
2” [51mm] sides /
bottom (outside of en-
closure)
0” to non-combustible
fi nishing such as brick
and stone
6” [152mm] minimum
(inside enclosure)
0” to bottom of the
appliance
0” to side standoffs
1/2” fi nishing fl ange
When passing through
a ceiling, use fi restop
spacer W500-0028
(not supplied)
When passing through
a wall, use fi restop
spacer W615-0162
(supplied with W010-
4178 fi restop spacer
assembly)
0” to back standoffs
1” [25mm] minimum
all sides for sections
of vertical venting.
Ref
LV38-1
LV50-2
LV62
LV74
L
73” (185.4cm)
91” (231.1cm)
minimum clearance
The LV series requires a minimum enclosure/ceiling height, as illustrated (dimension L), measured from the bot-
tom of the appliance. For temperature requirements, this area must be left unobstructed. Some venting con-
fi gurations that require more vertical rise will require a larger enclosure to provide minimum vertical clearance
between vent pipes and combustibles.
note:
Horizontal vent sections:
A minimum clearance of 3” (76mm) on the top outside of the enclosure and 2”
(51mm) on the sides and bottom outside of the enclosure all around the vent pipe on all horizontal runs to com-
bustibles is required. Horizontal vent sections within enclosures require a minimum clearance of 6” (152mm) at the
top of the vent pipe.
Vertical vent sections:
The fi rst 30” (76.2cm) of vertical vent pipe is shielded. A 1” (25mm) clearance to the
shield is required.
3” [76mm] (minimum all sides
for sections of horizontal vent-
ing) outside of enclosure.