minimum venting requirements - natural gas
0’
0’
Base of
air collar
10’
10’
15’
15’
20’
25’
20’
30’
40’
5’
4 7/8’ (58 1/2”) max.
(LV74 see-thru)
1 1/2’
(18”)
4’
(48”) min.
5’
1 elbow zone
1-2 elbow zone
1-3 elbow zone
1-4 elbow zone
1-5 elbow zone
1-6 elbow zone
H
V
V+H ≤ 40 ft. (For longer vent runs, a power
vent is required).
H ≤ 20 ft.
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
38 1/2’
(462”)
4 3/8’ (52 1/2”) max.
(LV62 see-thru)
LV62 / LV74 SEE-THRU (NATURAL GAS ONLY)
Refer to appliance
specific GPV/
PVA instructions
for other venting
configurations.