W415-1472 / 04.21.15
10
EN
2.4 GENERAL
INFORMATION
Thank you for purchasing a Wolf Steel Ltd. Pellet Appliance. This appliance is designed for use with Pelletized
Wood Only.
Please read this entire manual before installation and use of this pellet fuel-burning room appliance. Failure to
follow these instructions could result in property damage, bodily injury or even death.
Keep this manual handy for future reference.
This Pellet Appliance, when installed, must be electrically grounded in accordance with the local codes, or in
the absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI/NFPA
70 National Electrical Code in the United States.
This appliance will not operate using natural draft or without a power source for the blower systems and fuel
feed system.
These appliances are equipped with levelling screws that penetrate the front corners of the fi rebox. If these
screws are missing it will have a negative infl uence on the performance of this appliance. Ensure that the
levelling screws are tightened into position.
The protective wrap on plated parts is best removed when the assembly is at room temperature but this can be
improved if the assembly is warmed, using a hair dryer or similar heat source.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
fl ooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
4.5B
Pellet quality is important, please read the following:
Your Wolf Steel Ltd. Pellet Appliance has been designed to burn premium hard or soft wood pellets only. Do
not use any other type of fuel such as fi re logs or fi re starting pellets, as this will void the warranties stated in
this manual.
The performance and heat output of the pellet appliance is directly related to the quality and moisture of the
pellets. Store pellets in a cool dry area to prevent moisture absorption.
64.1
!
WARNING
IT IS IMPORTANT TO SELECT AND USE ONLY PELLETS THAT ARE DRY AND FREE OF DIRT
OR ANY IMPURITIES SUCH AS HIGH SALT CONTENT. DIRTY FUEL WILL ADVERSELY AFFECT
THE OPERATION AND PERFORMANCE OF THE APPLIANCE AND WILL VOID THE WARRANTY.
THE PELLET FUEL INSTITUTE (P.F.I.) HAS ESTABLISHED STANDARDS FOR WOOD PELLET
MANUFACTURERS. WE RECOMMEND THE USE OF PELLETS THAT MEET OR EXCEED THESE
STANDARDS. ASK YOUR DEALER FOR A RECOMMENDED PELLET TYPE.
2.4.1 PELLET SPECIFICATIONS
P.F.I. PELLET STANDARDS:
If the fuel does not comply to
this standard the appliance
may not operate as designed.
We recommend the use of
premium grade (1% ash
content) for longer appliance
life and less frequent cleaning.
Inorganic Fines (fi ne
particles)
1% maximum through a 1/8" (3.2mm) screen
Bulk Density
38 pound per cubic foot minimum
Size
1/4" (6.4mm) to 5/16" (8mm) diameter, 1/2" - 1 1/2" (13mm
- 38mm) long maximum
Ash Content
No more than 2%
Moisture Content
8% maximum
Chlorides
300 parts per million by weight
Trace Metals
Less than 100mg/kg
Heat Content
Approximately 8200 BTU per pound minimum
Construction Waste
Not to contain any waste materials
Содержание NPI45
Страница 48: ...W415 1472 04 21 15 48 EN 67 20 29 58 41 38 43 44 63 57 60 6 11 3 NPI45 REPLACEMENT PARTS...
Страница 54: ...W415 1472 04 21 15 54 EN 14 0 SERVICE HISTORY 43 1...
Страница 55: ...W415 1472 04 21 15 55 EN 15 0 NOTES 44 1...
Страница 105: ...105 W415 1472 04 22 15 FR 46 29 50 34 50 52 46 51 45 47 48 49 49 13 21 30 44 43 56 6 11 2 PI CES DE RECHANGE DU NPS45...
Страница 106: ...106 W415 1472 04 22 15 FR 67 20 29 58 41 38 43 44 63 57 60 6 11 3 PI CES DE RECHANGE DU NPI45...
Страница 114: ...114 W415 1472 04 22 15 FR 15 0 NOTES 44 1...
Страница 115: ...115 W415 1472 04 22 15 FR 44 1...