6. STARTUP AND SHUTDOWN
The Condo Pack is designed to be used with residential single-stage cooling and single-stage heating wall
thermostats with automatic or manual mode changeover. Automatic changeover thermostats must include a
dead-band to prevent cycling between cooling and heating modes. Single-pole, single-throw thermostats are
not suitable for use with Condo Pack. Indoor blower motor speed for cooling and heating modes can be altered
by changing the motor speed taps on the x13/Endura Pro Motor harness.
Before starting heating module for the first time, be sure you can answer “YES” to each of these questions:
a. Is the unit level?
b. Have you cleared away all loose construction and insulation materials?
c. Is unit installed within proper clearances to combustible materials?
See Section
“4.2 Unit Location and Clearances”
.
d. Does electrical wiring follow current National Electrical Code ANSI 70 or CSA C22.1 as well as
local codes?
See Section
“5. Electrical”
.
e. Is unit electrically grounded?
See Section
“5. Electrical”
.
f. Is room thermostat properly installed?
See Section
“5. Electrical”
.
g. Is ductwork correctly sized and sealed?
See Section
“4.8.1 Supply Air Ducting”
.
h.
Is air filter in place and correctly sized?
See Section
“4.8.2 Return Air Ducting”
.
6.1 HEATING MODULE START-UP CHECKLIST
1. Turn the Thermostat to
HEAT
mode.
2. Set the room Thermostat to a point above room temperature to start the heating operation.
1. Set the room Thermostat to below desired room temperature or to the “
OFF
” position.
2. Turn the Disconnect Switch to the “
OFF
” position.
6.1.1 Heating Module Startup
6.1.3 Air Conditioning Startup
6.1.2 Heating Module Shutdown
6.1.4 Air Conditioning Shutdown
1. Turn the Thermostat to
COOL
mode.
2. Set the room Thermostat to below the current temperature to turn on AC.
3. Wait for the fan and compressor to turn on and run the unit for at least 10 minutes.
1. Turn the Thermostat
OFF
.
2. Wait for the fan and compressor to turn off.
3. Turn the Disconnect Switch to the “
OFF
” position.
WARNING
!
!
AIR CONDITIONER MUST NOT BE OPERATED WHEN OUTDOOR TEMPERATURE
IS BELOW 55°F.
While operating, the air conditioner will remove humidity from the air. This humidity will condense on the
evaporator coil and eventually fall in the drain-pan below the coil. There is a rubber hose (“P -Trap”) that takes
the water collected to the building service drain. Before initial operation and/or at the beginning of each cooling
season, it is important that this P-trap is primed. If the P-trap dries out, air can be drawn back up the hose
pulling condensate off the coil, getting the air filter and other components wet. On how to prime the
condensate trap, refer to the instructions
“4.9 Condensate Drain Connection”
.
NOTE
Содержание Condo Pack
Страница 58: ...58 IOM IOM W415 2288 08 29 2019 9 3 P E HEATING MODULE...
Страница 62: ...62 IOM IOM W415 2288 08 29 2019 44 1...
Страница 63: ...63 IOM W415 2288 08 29 2019 44 1...
Страница 122: ...58 IOM IOM W415 2288 08 29 19 9 3 MODULE DE CHAUFFAGE LECTRIQUE CONDO PACK P E...
Страница 126: ...62 IOM IOM W415 2288 08 29 19 44 1...
Страница 127: ...IOM W415 2288 08 29 19 44 1...