![Napoleon Condo Pack Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/napoleon/condo-pack/condo-pack_installation-and-operating-instructions-manual_3307042011.webp)
11
IOM
W415-2288 / 08.29.2019
The minimum clearances required for installation and accessibility are shown below. These clearances should
be followed unless otherwise approved by the manufacturer.
NOTE
IMPORTANT:
Prior to constructing interior closet walls in close proximity to the wall sleeve, the sealing of the wall sleeve and cabinet s
hould be
completed. Sealing after the walls are constructed can be difficult. Poor sealing will result
in cold air
infiltration
that will affect
Condo Pack.
Refer to section "
Sealing: Wall Sleeve and Condo Pack cabinet
".
MINIMUM CLEARANCE
ADEQUA
TE SER
VICE CLEARANCE MUST BE PROVIDED IN FRONT OF THE UNIT
.
R
EQUIRED
DUE
TO
UNIT
’
S
DIMENSION
&
SAFETY
STANDARD
**
A clear and unobstructed passageway (dimension
AxB) shall be provided to the unit, in accordance with the requirements
of the local authorities having jurisdiction and with the Nationa
l Electrical Code in the United States and the Canadian
Electrical Code CSA
C22.1 Part 1 (latest edition) in Canada.
*
The 32 " x 40 " unobstructed clearance is required in front of th
e unit for complete removal of heating module and the cabinet to access cooling
section components.
Check local building codes for other appl
icable requirements.
0 "
MIN. CLEARANCE
2 "
MIN. CLEARANCE
DOOR OPENING
29 "
REF.
DRAIN REQUIRED (1.5"
Ø
MIN.)
FOR REMOVAL OF AC CONDENSATE
Exterior wall
Exterior wall
OUTSIDE
1 "
REF.
CLEARANCE BETWEEN
LEFT (HINGE)
SIDE DOOR JAM
AND CONDO PACK
1.5 " Ø
0.25 "
MIN.
CLEARANCE
*32 "
**
A
8 "
MIN.
2 "
MIN.
CLEARANCE TO COMBUSTIBLE
***
SECURE
TO WALL
FLOOR
**B
*
40 "
***
Engineer/Architect - to consult with
cust
omer solutions if clar
ifica
tion is r
equir
ed
to
determine bracket location for setting the desired depth
of W
all Sleeve into wall.
FABRICATED WOOD OR STEEL SUPPORT
(Refer to the manual for design options).
FIG. 4.2.1.A
4.2.1 Minimum Clearances
Содержание Condo Pack
Страница 58: ...58 IOM IOM W415 2288 08 29 2019 9 3 P E HEATING MODULE...
Страница 62: ...62 IOM IOM W415 2288 08 29 2019 44 1...
Страница 63: ...63 IOM W415 2288 08 29 2019 44 1...
Страница 122: ...58 IOM IOM W415 2288 08 29 19 9 3 MODULE DE CHAUFFAGE LECTRIQUE CONDO PACK P E...
Страница 126: ...62 IOM IOM W415 2288 08 29 19 44 1...
Страница 127: ...IOM W415 2288 08 29 19 44 1...